EVAX System Wiring

3.5 Maximum Wiring Length for Addressable Circuits

Note: Distances noted in this table account for the total length of wire, from the panel to furthest device
and back to the panel.

3.6 Maximum Wiring Length for Bell Circuits

Note: Distances noted in this table account for the total length of wire, from the panel to furthest device and
back to the panel.

Gauge

Belden No. Maximum Distance

18

9571

975m (3200 ft)

16

9572

1400m (4600 ft)

14

9580

2435m (8000 ft)

12

9582

3045m (10000 ft)

12AWG

14AWG

16AWG

18AWG

Max R

Max I

m

ft

m

ft

m

ft

m

ft

8.00

0.25

768

2519

483

1584

304

996

191

627

4.00

0.5

384

1259

241

792

152

498

95

313

2.67

0.75

256

840

161

528

101

332

64

209

2.00

1

192

630

121

396

76

249

48

157

1.60

1.25

154

504

97

317

61

199

38

125

1.33

1.5

128

420

80

264

51

166

32

104

1.14

1.75

110

360

69

226

43

142

27

90

1.00

2

96

315

60

198

38

125

24

78

MV 2700 M

Conduit

20’ Max

MR-2100 / MR-2200

GND

RX

RS232-2

TX

Main Board

GND

RX

TS3

TX

HMX-MP

HS-3100/3200

Advertising