Fan circuit operation (sn+), To remote circuit, To a tr – Great Plains YP825A Operator Manual User Manual

Page 43

Advertising
background image

Great Plains Manufacturing, Inc.

Table of Contents

Index

Operating Instructions

39

2014-08-15

Table of Contents

Index

401-651M

Fan Circuit Operation (SN+)
Applies to planters with serial numbers:
(YP425A s/n B1009N+)
(YP625A s/n B1044Q+) (YP825A s/n B1015S+)

See also “Fan and Adjustment” on page 54.

Refer to Figure 37

Operating flow
Shut-off flow (fan coasting to stop)

Two hydraulic hoses serve the fan, and must be properly
connected for the fan to operate in the correct
direction

, and at recommended speeds. See

Hydraulic Hose Hookup” on page 15.

1.

Connect the motor return line

, to remote circuit

return (Extend port) or to sump.

The planter includes a pressure-relief QD coupler for
the return line. This prevents motor damage in the
event that the return line is not connected, or is
connected incorrectly; however, an oil spill results if
the return line is not correctly connected.

2.

Connect the motor inlet line

to a tractor remote

capable of 20 liters per minute. If a priority remote is
available, use it for the fan.

3.

The fan hydraulic circuit includes a check valve

,

which provides a relief path for oil at motor shutoff.
If the fan is connected in reverse, flow through this
valve results in low fan rpm, providing strong
indication reversed connection.

Correct fan direction is shown at

. If reversed fan is

suspected, observe it during shutoff, as the direction
of motion is easier to see at lower rpms as it slows to
a stop (initial startup is virtually instantaneous,
making observation at start difficult).

Fan speed is controlled by the tractor circuit and butterfly
valve (and not the seed monitor).

Note: Fan speed can change as oil heats to operating

temperature. Re-check meter pressurization more
often during early operations.

You may stop the fan by setting the circuit to Neutral or
Float. The check valve slows the blades to a stop by
locally recirculating the oil.

Figure 37

Hydraulics at Fan

31869

If the fan is connected in reverse, it may not run at all
(due to no oil source at the return connection). If oil is
present, oil bypass at the check valve

prevents the

fan from reaching high rpm. A reversed fan may send
some air to the meters, but is incapable of providing
reliable air flow for planting.

5

1

3

4

5

1

3

4

5

1

3

4

Figure 38

Fan Hoses

31886

Advertising
This manual is related to the following products: