Send data reports, Calibration factor, Meter reading – ADS Environmental Services XiLog+ QR 775026 A0 User Manual

Page 46: Meter units, Secondary logging

Advertising
background image

ADS XiLog+ System User Manual

40

If this option is not selected, the flow rates from the two meters will be logged
and transmitted independently. Therefore, transmitting the data via SMS will
result in sending double the number of SMS.

Send Data Reports

Selecting this checkbox ensures the logger sends data reports by SMS or
GPRS, based on the interval designated for remote data reporting.

The minimum logging interval for data sent through SMS reporting is 1
minute. For data logged at a shorter interval, the logger will average the data
at a 1-minute interval before sending the report.

Note: Sending data logged at an interval of less than 15 minutes via
SMS requires sending more than one SMS per day for each per
channel. For example, sending 1 minute SMS data every day requires
sending 15 SMS per channel per day.

Calibration Factor

This field represents the number of liters that correspond to a single pulse
from the meter. This value should always reflect the factor set in the meter.
Modify this factor manually or using the up/down arrows.

Meter Reading

This field displays the site meter reading entered into the logger. Writing this
reading into the logger upon installation will ensure the meter reading in the
XiLog+ tracks the actual meter reading. Enter a meter reading up to 10 digits
in length, with an accuracy of up to 4 decimal places.

Meter Units

This drop-down list includes the options for selecting the units of measure
corresponding to the meter reading. A variety of units are available, based on
the size of the meter and accuracy required.

Secondary Logging

Some XiLog+ models allow a secondary logging interval for logging the same
channel input at a second rate. This data can be reported remotely, or logged

Advertising