www.amico.com 17

e.

Consideration shall be given to the potential effect of prevailing winds and possible sources of

airborne contamination and potential obstruction by accumulated snow.

f.

Piping downstream of the compressor shall be routed in such a way that it is not subjected to a

temperature lower than 40˚F (4˚C).

g.

Compressor intake piping shall be made of materials approved for vacuum piping compliant with

the latest NFPA 99 edition. In addition, the piping materials are assured to not contain contaminants

in the form of particulate matter, odor, or other gases.

D.

Control Panel and Alarm Sensors

The control system is U.L. labeled. The control system provides automatic lead/lag sequencing and automatic alternation

of pumps based on first-on/first-off principle with provision for simultaneous operation if required. Automatic activation

of reserve unit, if required, will activate an audible alarm as well as a visual alarm on the display screen.

1.

Control Panel Features:

Only panel components that are commercially available and not of propriety design will be considered.

a.

NEMA 12 control panel enclosure.

b.

Full voltage motor starter shall be UL 508 E self-protected combination starters with overload

protection and external operators.

c.

Door interlock disconnect switch.

d.

90 dB alarm buzzer.

e.

Visible indicator of “power on” and “compressor running” for each compressor.

f.

Two control transformers with secondary circuit breaker.

g.

Manual / Off Auto selector switches (Each Compressor).

h.

Transducer and RTD based control panel.

i.

The RTD will digitally display the running temperature of each discharge port and shall be field

programmable to standard manufacturer’s operating parameter.

j.

The calibration of the pressure transducer can be set so a non-standard transducer can be used.

2.

Touch screen controls feature a minimum 5.7”screen. Screen displays and functions include:

a.

WinCE 5.0 operating system.

b.

OPC, TCP/IP and Communication drivers.

c.

Ethernet connectivity with embedded web-page for remote monitoring, multi-level password

protected remote adjustment of all operating parameters.

d.

Electronic notifications of alarms and warnings.

e.

Communication expansion capability to talk over five Networks/Protocols.

f.

Service alerts, runtime hour meters for each pump, system status, system vacuum level all shall be

displayed.