Air Treatment Centre

Provide redundant medical air treatment systems including desiccant dryers, filters, and purifiers sized for peak
calculated demand. Dew point and carbon monoxide monitoring Medical Air Treatment shall include:

1.

Desiccant dryers producing a -40˚F (-40˚C) pressure dew point.

2.

Dryer purge flow control through an integral dew point based purge control system. Purge

controllers using desiccant temperature are not acceptable. Drying units shall provide a numerical

indication of the outlet dew point and initiate an alarm when the outlet dew point exceeds the

manufacturer’s pre-set limit.

3.

Mounted pre-filter with corrosion-resistant housing rated for 0.01 with automatic drain and

element change indicator at the inlet to each dryer.

4.

Final line filters rated for 0.1 particulate after filter with element change indicators, duplexed final

line regulators, and duplexed safety relief valves shall be factory mounted and piped at the outlet of

each

dryer.

µ

µ