0.5

0.00

PEAK CALCULATED DEMAND IN SCFM
BASED ON FREE AIR SCFM

@ 50

PSI:

1

1.5

1.5

1.5
1.5

1
1
1
1

50
50
25

10
10

10
10
25

100

10
50
10

0
0
0

0

0

0
0
0
0
0
0

0

0.00
0.00

0.00

0.00

0.00

0.00

0.00
0.00
0.00
0.00
0.00
0.00

0.00

1

1.5

7.

1.

8.

2.

9.

3.
4.
5.
6.
7.
8.
9.

Note:

1.

The SCFM above is based on a peak OUTLET demand of 50 psi. Air compressors operate at 100 psi. When

sizing a compressor, you MUST figure the compressor capacity for operation at 100 psi.

2.

You need to consider several environmental factors when sizing the compressors. These include altitude,

intake air temperature, and relative humidity. Variance among these factors has considerable effect on

compressor selection.

3.

Air outlets in labs used for analysis, research or teaching should be supplied by a separate compressed air

system, not the medical air system.

4.

All sizing methods are only approximations and should be used judiciously. If an existing compressor is

being replaced, the operating characteristics of that compressor can be an important gauge of likely future

use. For example, if an existing 5 HP compressor provides an ample amount of medical air, but the

sizing tables yield much larger requirements; it may be suitable to use a smaller compromise unit as

opposed to simply relying on the results from the Amico Sizing Guide.

6.3.4 Altitude Adjustments

If the compressor is to be operated at higher elevations, the peak calculated demand should be multiplied by the
corresponding correction factor. Specifically, at altitudes above sea level, all medical air systems have reduced flow.
In such cases, the required sizing will need to be adjusted by taking the total PCL (SCFM) and multiplying it by the
correction factor (See Figure 3 below).