Amico Nema 4 Master Alarm User Manual

Page 16

Advertising
background image

16

Amico Pipeline

When you have completed step #7, the display module

will automatically go into a “RESET” mode. This will store the

data that you had entered.

PSI / kPa / BAR selection

Factory Default - PSI

For PSI mode, set the switch #4 to the ON position. The LED PSI indicator located next to the GAS

pressure reading will illuminate.

For kPa mode, set the switch #4 to the OFF position and switch #9 to the ON position. The LED kPa

indicator located next to the GAS pressure reading will illuminate.

For BAR set the switch #4 to the OFF and the switch #9 to the OFF position. The LED kPa indicator

located next to the GAS pressure reading will illuminate. (There is no separate indicator for BAR).

VACUUM ONLY

Vacuum alarm set-point adjustment

Factory Default:

High = 30”Hg, Low = 12”Hg

Repeat time = 30 min.

During programming, the “Trend Bar” will Flash!

1. Set switch #6, #7 and #8 to the ON position.

2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to

accept a new High set point. Do not adjust this set point since the High set point is not used.

3. Set switch #7 to the OFF position.

4. The LED will display (LO-), followed by the current set point. Indicating the system is ready

to accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to

the desired value.

5. Set switch #8 to the OFF position.

6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to

accept a new Repeat time set point. Adjust set point using the “UP” and “DOWN”push buttons,

to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]

7. Set switch #6 to the OFF position.

When you have completed step #7, the display module will automatically go into a “RESET” mode.

This will store the data that you had entered.

PSI

KPA

BAR

A l e r t - 2 S e r i e s

P a g e : 1 7

THE AREA/2 IN 1 DISPLAY MODULE

A dip switch is located on the back of the display module
which is used to identify the gas of the display module. The
dip-switch contains ten switch settings.

PRESSURE ONLY

Factory Default:

High = 60 Psi, Low = 40 Psi

Repeat time = 30 min.

HIGH PRESSURE/NITROGEN

Factory Default:

High = 195 Psi, Low = 140 Psi

Repeat time = 30 min.

During Programming the

“Trend Bar” will Flash!

1.

Set switch #6, #7 and #8 to the ON position.

2.

The LED will display (

HI-

HI-

HI-

HI-

HI-

), followed by the current set point.

Indicating the system is ready to accept a new High set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desired value.

3.

Set switch #7 to the OFF position.

4.

The LED will display (

LO-

LO-

LO-

LO-

LO-

), followed by the current set point.

Indicating the system is ready to accept a new Low set point.
Adjust set point, using the “UP” and “DOWN” push buttons, to the
desired value.

5.

Set switch #8 to the OFF position.

6.

The LED will display (

I-I-

I-I-

I-I-

I-I-

I-I-

), followed by the current set point.

Indicating the system is ready to accept a new Repeat time set
point. Adjust set point using the “UP” and “DOWN” push buttons,
to the desired value. [(Display dd=Disabled) Range from 1 to 60
Minutes]

7.

Set switch #6 to the
OFF position.

2 in 1 Alarm

Board

Area Alarm

Board

When you have completed
step #7, the display module
will automatically go into a
“RESET” mode. This will store
the data that you had entered.