Troubleshooting guide – Amico Nema 4 Master Alarm User Manual

Page 22

Advertising
background image

22

Amico Pipeline

Troubleshooting Guide

SYMPTOM

CAUSE

CORRECTIVE ACTION

1. An error code appears on one or

more display modules.

2. No power on the alarm.

(No LED’s illuminated).

a. The Microprocessor detected a

fault and has shutdown.

b. Faulty wire connection between

the sensor and display module.

a. AC power not available.

b. Fuse is blown.

c. DC power plug not connected

to the annunciator module.

d. Defective Ribbon cable.

1. Turn power switch to OFF position.

Wait for at least 5 seconds before

turning on the power. The program

will reset itself.

2. Check error codes at the end of this

section.

1. Ensure that the ON/OFF switch on the

power supply module is turned ON.

2. AC wiring not connected.

3. Check the building electrical breaker

to ensure that the power is ON.

4. Check the voltage at the terminal

block above the transformer. Ensure

that 115 VAC or 220 VAC is being

supplied.

1. Check the fuse. The fuse is located on

the upper-right corner of the system

power supply. Replace the fuse if it

is defective. See Appendix A and P.

1. Ensure that the DC power plug is

firmly in it’s socket on the annunciator

module.

2. Replace System Power Supply unit if

all the above steps fail to resolve the

problem.

1. Replace the ribbon cable.