Baumer_DSL-WinXP_MA_ENBaumer_DSL-WinXP_MA_EN.doc 13/22

Baumer Hübner GmbH

01.11.2010 / bja

Berlin, Germany

6.3 Main window

The register cards at the bottom of the window can be used to switch between the three main software
functions:

Switching speed Speed monitor Messages

6.3.1

Register: Switching speeds

After the device data have been read out, the register Switching speeds appears, in which the parameters
that are stored in the DSL can be read out and edited.

Fig. 11: “Switching speeds” register for DSL.E

The third output shown in Fig. 11 is the check output of the DSL.E (described above under 6.2). On a DSL.R,
a third field for making settings for switching speeds will appear instead (see figure 8).

The parameters for each output are set up separately. In addition, individual ON and OFF switching speeds
can be set up for clockwise (right-handed) and anti-clockwise (left-handed) rotation, i. e. up to 4 different
switching speeds for each output). System requirements impose a minimum hysteresis of 5% or 2 rpm.
Furthermore, a switching delay from 0 to 500 msec can be entered for each switched output, in order to be
able to ignore very short speed peaks.