Crestron electronic TPMC-8T User Manual

Page 20

Advertising
background image

Isys i/O™ 8.4” TableTop WiFi Touchpanel

Crestron TPMC-8T

which starts on page 62 or “Appendix B: TPMC-8T Security Pack (Intel PROSet)”
which starts on page 66 for details).

Touch Close to return to the setup menu.

Touch Screen

When Touch Screen is touched, the calibration screen will be displayed. Touch the
screen to begin the calibration process. If the screen is not touched within 10
seconds, the calibration sequence will stop and the screen will again display the
setup menu.

If the screen is touched within the 10-second timeout, it displays a series of messages
indicating that you should touch the red square in five places around the screen.
These messages will appear sequentially starting with “Touch the red square” at the
top of the screen toward the upper left corner. Touch and hold the center of the red
square to initiate calibration. The message will say “Hold…” for a few seconds, then
change to “Lift off to proceed”. Touch the displayed squares as prompted
everywhere they appear around the screen until the calibration is complete and you
are returned to the setup menu.

NOTE: When touching the screen during calibration, be as accurate as possible.
Use the tip of the included stylus. To cancel calibration and return to the setup menu
without saving calibration data, ignore the “Touch the red square” message. After
about 10 seconds, the setup menu will be displayed. If a USB keyboard is attached to
the touchpanel, you can also press the Escape key (Esc) to cancel calibration and
return to the setup menu.

NOTE: The touchpanel’s calibration routine can also be accessed through Crestron
Toolbox if the touchpanel is connected to a control system via TCP/IP. From the
System Info page, select Functions | Setup Mode…. Select Enter Calibration
Mode
to begin calibration.

Update Panel

The Update Panel button permits the selection of the touchpanel program, a .vtz
file. The Project tab of the “Project and Firmware” window (refer to illustration on
the following page) displays the Current Loaded Project and also has a Load New
Project
section.

Current Loaded Project displays the Name and Creation Time of the current project.

In the Load New Project section, touch Browse and select the compiled project (i.e.
the .vtz file) to be loaded from a network drive, USB device or flash drive. You can
choose the location where your uncompressed project files will be stored. The
default file location is the internal flash. Touch Load to uncompress the project file,
place it in the destination selected in Target Location to Load the Project to and
display it on the touchpanel.

NOTE: If there is a mapped network drive on the touchpanel, the first time you
select Browse, it may take some time for the “Open” window to appear.

NOTE: When selecting Browse, the contents of the “Recent” folder will not be
available.

NOTE: Projects can also be loaded via Crestron Toolbox.

16

Isys i/O™ 8.4” TableTop WiFi Touchpanel: TPMC-8T

Operations Guide – DOC. 6567C