CellarPro AIR HANDLER 6500 HORIZONTAL, 7090 User Manual

Page 12

Advertising
background image

12

Split Configuration.
Models in the Split Configuration can be mounted as follows, with interconnecting wiring
and refrigerant piping field provided by an experienced Refrigeration contractor:

Remote ducted: The unit is mounted remote to the cellar, and the evaporator module
intake and discharge air are ducted to the cellar. The condenser can be provided with
grills to vent the air, or duct adapters to duct the intake, discharge, or both. The
condenser module can also be located outdoors by installing optional outdoor louvers to
the intake and discharge air panel openings. The separate modules may be floor
mounted on leveling feet, or flush to the floor with the leveling feel removed. Each
module may be ceiling hung using four 1/4-20 threaded rods per module (field
provided), attaching to captive nuts provided in the top corners of the module.

Inside cellar: The evaporator module can be mounted inside the cellar as follows:

 The module may be floor or shelf-mounted, or flush to the floor or shelf with the

leveling-feet removed. If shelf mounted, the evaporator module requires a
mounting shelf designed to support the weight of the module, and secured by
four 1/4-20 bolts secured to weld nuts located in the bottom corners.

 The module may be ceiling hung using four 1/4-20 threaded rods (field provided),

attaching to captive nuts provided in the top corners of the module.

Condensing Units - Indoor

 Condensing units can be installed remotely from the cellar in an area protected

from direct exposure to moisture and sunlight.

 The area must have adequate ventilation to maintain a temperature of 110°F or

less.

 If the area does not have adequate ventilation, a vent fan should be added to

supply fresh air to the space.

 On units that are not ducted, a minimum of 12" of open air space is required in

front of the intake and discharge air panels.

Condensing Units - Outdoor

 Both the Horizontal and Split configurations can be installed with the Condenser

module located outdoors, with optional outdoor louvers installed in the air intake
and discharge positions.

 The unit is designed to operate in temperatures ranging from 0°F to 110°F.

Please note: Our compressor heater (ordered separately) is required for
temperatures below 40° F.

 A minimum of 12" of open air space is required in front of the intake and

discharge air panels.

 Knockouts are provided in the unit housing for field connection of conduit. The

conduit must be liquid tight and approved for outdoor use. Conduit fittings shall
be in accordance with UL 514B.