Deviation of the airflow rate on the am4024(e) – Kontron AM4024e User Manual

Page 58

Advertising
background image

D R A F T — F O R I N

T E R N A L U S E O N L Y

58

www.kontron.com

User Guide

AM4024(E)

The following table indicates the deviation of the airflow rate on the AM4024(E) module.

Note:

The AM4024(E) module has an airflow rate deviation of max. ± 5.0% of the average value
of the four thermal zones (max. ± 25% is allowed).
Positive deviation means increased airflow.
Negative deviation means decreased airflow.

Note:

The AM4024(E) module provides an open area of 40%. According to the PICMG AMC.0 Spec-
ification, an open area of 20 to 70% perpendicular to the airflow path is recommended.

.

Table 40: Deviation of the Airflow Rate on the AM4024(E)

VOLUMETRIC

FLOW RATE [CFM]

PRESSURE DROP [N/m²]

ZONE A

ZONE B

ZONE C

ZONE D

5

-1.6%

-2.5%

-0.7%

4.7%

10

-0.9%

-2.2%

-0.9%

4.0%

15

-0.6%

-2.1%

-1.2%

3.9%

20

-0.6%

-1.9%

-1.0%

3.5%

25

-0.5%

-1.9%

-1.2%

3.6%

30

-0.4%

-1.9%

-1.2%

3.5%

35

-0.3%

-1.9%

-1.2%

3.4%

40

-0.3%

-1.8%

-1.3%

3.3%