0 block transfer commands, Block transfer commands – Rice Lake Allen-Bradley Remote I/O User Manual
Page 16
12
Remote I/O Installation and Programming Manual
4.0
Block Transfer Commands
The Remote I/O Interface supports block transfer commands for the
520
,
720i
,
820i
, and
920i
indicators. These
commands allow the PLC controller to exchange larger blocks of data with the indicator, such as 32-bit
floating-point values and partial setpoint configuration.
NOTE: Weight data returned by block transfer commands is not valid when the indicator is in setup mode.
Table 4-1 shows the block write and block read commands supported by the Remote I/O Interface.
Table 4-1. Block Transfer Commands
Command Number
Command Name
Block Write
Command
Length
Block Read
Command
Length
Decimal
Hex
268
0x10C
Set Tare Value
4
4
288
0x120
Read Gross Weight
2
4
289
0x121
Read Net Weight
2
4
290
0x122
Read Tare Weight
2
4
291
0x123
Read Piece Count
2
4
293
0x125
Read Current Display
2
4
294
0x126
Read Accumulator
2
4
295
0x127
Read Rate of Change
2
4
296
0x128
Read Peak Value
2
4
302
0x12E
Read Gross, Tare, Net
2
8
303
0x12F
Read Multiple Weights
4
4–62
304
0x130
Set Setpoint Value
4
2
305
0x131
Set Setpoint Hysteresis
4
2
306
0x132
Set Setpoint Bandwidth
4
2
307
0x133
Set Setpoint Preact
4
2
319
0x13F
Set Single Setpoint, All Values
10
2
320
0x140
Read Setpoint Value
2
4
321
0x141
Read Setpoint Hysteresis
2
4
322
0x142
Read Setpoint Bandwidth
2
4
323
0x143
Read Setpoint Preact
2
4
335
0x14F
Read Single Setpoint, All Values
2
10
336
0x150
Set Multiple Setpoint Values
4–62
2
337
0x151
Read Multiple Setpoint Values
2
4–62
NOTE: Command lengths expressed as number of words. Number of words required for variable length commands depends on
number of setpoints or scales specified.