2 dip switch configuration, Section 2.2, Sw2 sw1 – Rice Lake Allen-Bradley Remote I/O User Manual

Page 8

Advertising
background image

4

Remote I/O Installation and Programming Manual

2.2

DIP Switch Configuration

Two banks of DIP switches, SW1 and SW2, are used to configure the Remote I/O Interface for communication
with the indicator and the network. Figure 2-3 shows the switch assignments for SW1 and SW2.

SW2

SW1

Starting

Quarter

Rack Address

MSB

LSB

Network

Data Rate

Reser

ved

Last Rack

Rack Size

Reser

ved

Link Address

Block T

ransfer

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

OPEN

OPEN

Figure 2-3. SW1 and SW2 DIP Switch Assignments.

Starting Quarter

Switches SW1-1 and SW1-2 set the starting quarter
(or group number) used by the Remote I/O Interface.
Use Table 2-3 to select the correct switch settings.

Table 2-3. Starting Quarter

Starting

Quarter

Group

Number

SW1 Switch Settings

1

2

1st

0

CLOSED

CLOSED

2nd

2

OPEN

CLOSED

3rd

4

CLOSED

OPEN

4th

6

OPEN

OPEN

Rack Address

Switches SW1-3 through SW1-8 are used to set the
rack address of the Remote I/O Interface. Use Table
on page 5
to select the correct switch settings for the
rack address.

Note that setting a switch OPEN acts as a

logical “1” and that SW1-3 represents the least significant bit
(LSB) of the rack address.

Network Data Rate

SW2-1 and SW2-2 set the data rate of the
Allen-Bradley network. Use Table 2-4 to select the
correct switch settings for the network.

Table 2-4. Network Data Rate

Remote I/O Data Rate

SW2 Switch Settings

1

2

57.6 Kbps

CLOSED

CLOSED

115.2 Kbps

OPEN

CLOSED

230.4 Kbps

CLOSED

OPEN

OPEN

OPEN

Last Rack

Set SW2-3 OPEN if the Remote I/O Interface link
address includes the highest module group in this rack
address.

Rack Size

At this time only a quarter rack size is supported. This
option has been included for possible future expansion
to include half rack support. Switch 2-4 is ignored.

Block Transfer

Set SW2-6 CLOSED to enable or OPEN to disable
block transfer to the Remote I/O Interface. Setting this
switch OPEN causes the Remote I/O Interface to
ignore unsolicited block transfer requests from the
PLC.

Advertising