Cooling sequence of operation, 48e s -- a – Carrier 48ES---A User Manual

Page 22

Advertising
background image

22

speed when the DH control lead is not energized, or IFB “HIGH”
speed when the DH lead is energized (see Fig. 18).

COM

LOW

HIGH

GAS
HEAT

Q1

R1L

C8

RL3

Q3

DCR

QCR

QC1

G1

G2

A7

D4

D6

C2

OILL

R9

AB A15

C4

C9

C0

R4

RL4

C7

R2

R3

R5 R6

QCB

Y

Y

R

U

C 24VAC

JW1

P2

P1

W2

Y2/

Y1/

Y

DH

G

C

R

SSTZ-8

P3

SDL

24V

AC/R

CDM/C

F1

QC6

QC7

QC4

QC3

K2

K1

D2

RI0

RI2

JM6

RI

DL

JM5

U1

C3

D3

D5

JW3

JW2

JW4

JW7

3 AMP

C

A09058

Fig. 18 -- Interface Fan Board (IFB)

Table 6 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--- High Speed

Red = Med Speed

Pink = Med--- Low Speed

Blue = Low Speed

Cooling Sequence of Operation

With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence

of operation is as follows:

1. When the room temperature rises to a point that is slightly

above the cooling control setting of the thermostat, the
thermostat completes the circuit between thermostat

terminal R to terminals Y and G.

2. The normally open contacts of energized contactor (C) close

and complete the circuit through compressor motor
(COMP) to condenser (outdoor) fan motor (OFM). Both
motors start instantly.

3. The set of normally open contacts on the interface fan board

(IFB) are closed which energizes a circuit to the indoor fan

motor (IFM).

NOTE: Once the compressor has started and then stopped, it
should not be started again until 5 minutes have elapsed. The
cooling cycle remains on until the room temperature drops to a
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between
thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C. The condenser and compressor motors
stop. After a 90--sec. delay, the blower motor stops. The unit is in a
standby condition, waiting for the next call for cooling from the
room thermostat.