Table 13 – Troubleshooting Guide–Heating

SYMPTOM

CAUSE

REMEDY

Burners will not ignite

Water in gas line

Drain. Install drip leg.

No power to furnace

Check power supply fuses, wiring or circuit breaker.

No 24--v power supply to control circuit

Check transformer.

NOTE: Some transformers have internal over--current protection

that requires a cool--down period to reset.

Mis--wired or loose connections

Check all wiring and wire nut connections

Misaligned spark electrodes

Check flame ignition and sense electrode positioning.

Adjust as necessary.

No gas at main burners

1. Check gas line for air. Purge as necessary. NOTE: After purging

gas line of air, wait at least 5 minutes for any gas to dissipate be-

fore attempting to light unit.

2. Check gas valve.

Inadequate heating

Dirty air filter

Clean or replace filter as necessary

Gas input to furnace too low

Check gas pressure at manifold match with that on unit nameplate

Unit undersized for application

Replace with proper unit or add additional unit

Restricted airflow

Clean or replace filter. Remove any restriction.

Limit switch cycles main burners

Check rotation of blower, temperature rise of unit. Adjust as neces-

sary.

Poor flame characteristics

Incomplete combustion results in: Aldehyde odors,

carbon monoxide, sooting flame, floating flame

1. Tighten all screws around burner compartment

2. Cracked heat exchanger. Replace.

3. Unit over--fired. Reduce input (change orifices or adjust gas line

or manifold pressure).

4. Check burner alignment.

5. Inspect heat exchanger for blockage. Clean as necessary.

Table 14 – Troubleshooting Guide–LED Status Codes

SYMPTOM

CAUSE

REMEDY

No Power or Hardware fail-

ure

(LED OFF)

Loss of power to control module (IGC)*.

Check 5--amp fuse son IGC*, power to unit, 24--v circuit breaker,

and transformer. Units without a 24--v circuit breaker have an

internal overload in the 24--v transformer. If the overload trips,

allow 10 minutes for automatic reset.

Limit switch faults

(LED 2 flashes)

High temperature limit switch is open.

Check the operation of the indoor (evaporator) fan motor. Ensure

that the supply--air temperature rise is in accordance with the

range on the unit nameplate. Clean or replace filters.

Flame sense fault

(LED 3 flashes)

The IGC* sensed flame that should not be present.

Reset unit. If problem persists, replace control board.

4 consecutive limit switch

faults

(LED 4 flashes)

Inadequate airflow to unit.

Check the operation of the indoor (evaporator) fan motor and that

supply--air temperature rise agrees with range on unit nameplate

information.

Ignition lockout fault

(LED 5 flashes)

Unit unsuccessfully attempted ignition for 15 minutes.

Check ignitor and flame sensor electrode spacing, gaps, etc.

Ensure that fame sense and ignition wires are properly terminated.

Verify that unit is obtaining proper amount of gas.

Pressure switch fault

(LED 6 flashes)

Open pressure switch.

Verify wiring connections to pressure switch and inducer motor.

Verify pressure switch hose is tightly connected to both inducer

housing and pressure switch. Verify inducer wheel is properly

attached to inducer motor shaft. Verify inducer motor shaft is turn-

ing.

Rollout switch fault

(LED 7 flashes)

Rollout switch has opened.

Rollout switch will automatically reset, but IGC* will continue to

lockout unit. Check gas valve operation. Ensure that induced--draft

blower wheel is properly secured to motor shaft. Inspect heat

exchanger. Reset unit at unit disconnect.

Internal control fault

(LED 8 flashes)

Microprocessor has sensed an error in the software

or hardware.

If error code is not cleared by resetting unit power, replace the

IGC*.

Temporary 1 hr auto reset

fault

1

(LED 9 flashes)

Electrical interference impeding IGC software

Reset 24--v. to control board or turn thermostat off, then on again.

Fault will automatically reset itself in one (1) hour.

*

WARNING

: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control

board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken.

IMPORTANT: Refer to Table 12---Troubleshooting Guide---Heating for additional troubleshooting analysis.

LEGEND

IGC—Integrated Gas Unit Controller

LED—Light---Emitting Diode