3-4 Message Communication
3-25
3
Communi
cat
in
g wit
h the
IL Seri
es
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IL) -
(5) Reading the number of decimal places from a sensor amplifier
Message communication reads the number of decimal places of settings read
from the sensor amplifier.
"(5) Reading the number of decimal places in the parameter from a sensor
For the IL Series, if the current value is 12.53 mm, data is stored as
follows:
Data: 12530
Number of decimal places: 3
Perform calculation from the read data and the number of decimal places.
Command
Response
DL-EP1
Scanner
<Details of command>
Service code: 4CH
Class ID: 67H
Instance ID: 01H
Attribute ID: 0325H(805)
IL
Reads the number of decimal
places of the IL Judgment value
(P.V. value).
Reference
1253012.53012.53mm
Number of
decimal places
3 2 1