Control panel operating procedures – AERCO BMK 1.5 LN Dual Fuel June 2010 User Manual

Page 32

Advertising
background image

CONTROL PANEL OPERATING PROCEDURES

3-10

8. With the unit firing properly, it will be

controlled by the temperature controller
circuitry. The boiler’s VALVE POSITION will
be continuously displayed on the front panel
bargraph.


Once the demand for heat has been satisfied,
the Control Box will turn off the dual SSOV gas
valves. The blower relay will be deactivated and
the Air/Fuel Valve will be closed. Standby will
be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve
positions (% open) that start and stop the unit,
based on load. These levels are Factory preset
as follows:

Figure 3-6.

Air/Fuel Valve In Ignition Position

Start Level: 20%

Stop Level: 16%

6. Up to 7 seconds will be allowed for ignition

to be detected. The igniter relay will be
turned off one second after flame is
detected.

Normally, these settings should not require
adjustment.

Note that the energy input of the boiler is not
linearly related to the Air/Fuel Valve position.
Refer to Table 3-7 for the relationship between
the energy input and valve open position (%) for
a unit running on natural gas.

7. After 2 seconds of continuous flame, Flame

Proven

will be displayed and the flame

strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.

Table 3-7.

Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas

Fire Rate,

Air/Fuel Valve

Position (% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0% 0

0

10% 0

0

16%

(Stop Level)

75,000 5.0%

20% 157,000 10%
30% 310,000 21%
40% 534,000 36%
50% 783,000 52%
60% 970,000 65%
70% 1,140,000 76%
80% 1,240,000 83%
90% 1,370,000 91%

100% 1,500,000 100%