Safety device testing – AERCO BMK 1.5 LN Dual Fuel June 2010 User Manual

Page 50

Advertising
background image

SAFETY DEVICE TESTING

6.3 PROPANE LOW GAS PRESSURE
FAULT TEST

Refer to Figure 6-1 and ensure that the leak
detection ball valve located at the high gas
pressure switch is closed.

1. Ensure that the Fuel Selector Switch (Figure

4-3) is set to the PROPANE position.

2. Remove the 1/8“ plug from the ball valve at

the propane low gas pressure switch shown
in the lower-right portion of Figure 6-1.

3. Install a 0 – 16 “ W.C. manometer or a W.C.

gauge where the 1/8" plug was removed.

4. Slowly open the ball valve near the propane

low gas pressure switch.

5. Place the unit in Manual Mode and adjust

the valve position between 25 and 30%.

6. While the unit is firing, slowly close the

external manual gas shut-off valve.

7. The unit should shut down and display a

LOW GAS PRESSURE

fault message at

approximately 1.0” W.C. The FAULT indi-
cator should also start flashing.

8. Fully open the external manual gas shut-off

valve and press the CLEAR button on the
Control Box.

9. The fault message should clear and the

FAULT

indicator should go off. The unit

should restart.

10. Upon test completion, close the ball valve

and remove the manometer. Replace the
1/8“ plug removed in step 1.

6.4 NATURAL GAS HIGH GAS
PRESSURE FAULT TEST

To simulate a natural gas high gas pressure
fault, refer to Figure 6-1 and proceed as follows:

1. Ensure that the Fuel Selector Switch (Figure

4-3) is set to the NATURAL GAS position.

2. Remove the 1/8“ plug from the leak

detection ball valve shown in Figure 6-1.

3. Install a 0 – 16” W.C. manometer (or W.C.

gauge) where the 1/8” plug was removed.

4. Slowly open the leak detection ball valve

5. Start the unit in Manual mode at a valve

position between 25 and 30%.

6. Slowly increase the gas pressure using the

adjustment screw on the natural gas SSOV.

7. The unit should shut down and display a

HIGH GAS PRESSURE

fault message

when the gas pressure exceeds 4.7” W.C.
The FAULT indicator should also start
flashing.

8. Reduce the gas pressure back to 3” W.C.

9. Press

the

CLEAR

button on the Control Box

to clear the fault.

10. The fault message should clear and the

FAULT

indicator should go off. The unit

should restart.

11. Upon test completion, close the leak detect-

ion ball valve and remove the manometer.
Replace the 1/8“ plug removed in step 2.

6.5 PROPANE HIGH GAS PRESSURE
FAULT TEST

To simulate a propane high gas pressure fault,
refer to Figure 6-1 and proceed as follows:

1. Ensure that the Fuel Selector Switch (Figure

4-3) is set to the PROPANE position.

2. Remove the 1/8“ plug from the leak

detection ball valve shown in the upper
portion of Figure 6-1.

3. Install a 0 – 16” W.C. manometer (or W.C.

gauge) where the 1/8” plug was removed.

4. Slowly open the leak detection ball valve.

5. Start the unit in Manual mode at a valve

position between 25 and 30%.

6. Slowly increase the propane gas pressure

using the regulator adjustment screw on the
propane SSOV.

7. The unit should shut down and display a

HIGH GAS PRESSURE

fault message

when the gas pressure exceeds 2.6” W.C.
The FAULT indicator should also start
flashing.

8. Reduce the gas pressure back to 1” W.C.

9. Press

the

CLEAR

button on the Control Box

to clear the fault.

6-2

Advertising