Appendix e - boiler default settings, Appendix e – AERCO BMK 1.5 LN Dual Fuel June 2010 User Manual

Page 97

Advertising
background image

APPENDIX E

BOILER DEFAULT SETTINGS

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password 0

Language English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler Dual

Unit Size

1.5 MBTU

Boiler Mode

Constant Setpoint

Fuel Type

Natural Gas

Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio
(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp
(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

200°F

Temp Hi Limit

215°F

Max Valve Position

100%

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

CAUTION: DO NOT Change

Lo Fire Timer

2 sec

Setpt Limit Band (If Setpt Limiting = Enabled)

5°F

E-1