Safety device testing – AERCO BMK 1.5 LN Dual Fuel June 2010 User Manual

Page 53

Advertising
background image

SAFETY DEVICE TESTING

6. Open the valve previously closed in step 3

and press the CLEAR button.

7. Restart the unit and allow it to prove flame.

8. Once flame is proven, close the manual gas

valve located between the SSOV and the
Air/Fuel Valve.

9. The unit should shut down and execute an

IGNITION RETRY

cycle by performing the

following steps:

(a) The unit will execute a shutdown purge

cycle for a period of 15 seconds and
display WAIT FAULT PURGE.

(b) The unit will execute a 30 second re-

ignition delay and display WAIT RETRY
PAUSE.

(c) The unit will then execute a standard

ignition sequence and display WAIT
IGNITION RETRY

.

10. Since the manual gas shutoff valve is still

closed, the unit will shut down and display
FLAME LOSS DURING IGNITION

following

the IGNITION RETRY cycle.

11. Open the valve previously closed in step 8.

12. Press the CLEAR button. The unit should

restart and fire.

Figure 6-3

Manual Gas Shut-Off Valve Location

6.10 AIR FLOW FAULT TESTS

These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.

1. Disable the blower output drive voltage as

follows:

(a) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(b) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(c) Press

the

▼ arrow key until OFF is

displayed, then press the ENTER key.

2. Start the unit in the Manual Mode at a valve

position between 25% and 30%.

3. The unit should shut down and execute an

IGNITION RETRY

cycle by performing the

following steps:

(a) The unit will execute a 30 second re-

ignition delay and display WAIT RETRY
PAUSE.

(b) The unit will then execute a standard

ignition sequence and display WAIT
IGNITION RETRY

.

4. The unit should perform two IGNITION

RETRY

cycles and then shut down on the

third successive ignition attempt. The unit
will display AIRFLOW FAULT DURING
PURGE.

5. Re-enable the blower output drive voltage

by performing the following steps:

(a) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(b) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(c) Press

the

▲ arrow key until VALVE

POSITION 0-10V

is displayed, then

press the ENTER key.

6. Once the unit has proved flame, turn off the

blower by going to the Configuration Menu,
Analog Output

menu item and select OFF.

7. The Blower Proof Switch will open and the

blower should stop. The unit should shut
down and display AIRFLOW FAULT
DURING RUN

.

8. Go to the Configuration Menu, Analog

Output

item and select Valve Position 0-10v.

6-5