GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

Figure 18-30: DHW STORAGE SETPOINT Menu

DHW Storage Setpoint is the domestic hot water storage setpoint temperature when the Sensor

option is chosen in DHW Demand. Press the LEFT or RIGHT buttons to adjust the DHW Storage

Setpoint then press the OK button to store the setting.

NOTE

The boiler setpoint is automatically set to the DHW Storage

Setpoint + DHW Storage Adder when the Sensor option is chosen

in DHW demand.

========================================================================

18.4.5 DHW on Differential (Default: 6°F [3°C])

Figure 18-31: DHW ON DIFFERENTIAL Menu

DHW On Differential sets how far the DHW storage temperature must fall below the DHW

Storage Setpoint to create a domestic hot water call when the Sensor option is chosen in DHW

Demand. The domestic hot water call will end when the DHW storage temperature rises above

the DHW Storage Setpoint. Press the LEFT or RIGHT buttons to adjust the DHW On Differential

then press the OK button to store the setting.

WARNING!

The DHW on differential setting greatly affects the production of domestic

hot water. A low setting could result in a rapid response to a domestic hot

water call resulting in a potential scald hazard. It is strongly

recommended that the installer utilize a thermostatic mixing valve on the

hot water outlet of the indirect water heater. Failure to comply could result

in severe personal injury, death, or substantial property damage.