GF-135 Esteem 399 Low NOx Boiler

Chapter 12

OMM-0089_0A

Installation, Operation & Maintenance Manual Start-Up Procedures

Verifying Correct Flame Pattern and Combustion (Cont.)

d) Press the OK button while the FAN icon is highlighted to manually fire the burner and

power the CH circulator.

NOTE

An adequate CH load must be present to dissipate the heat

generated during the combustion test. If an adequate CH load is

not available, an indirect water heater can be used to dissipate the

heat by creating a DHW call which will enable the DHW circulator.

Table 12-1: Recommended Combustion Levels

Combustion Gases

Natural Gas

Propane Gas

O

2

Min.

2.30%

3.70%

O

2

Max.

5.30%

5.20%

CO

2

Min.

8.80%

10.00%

CO

2

Max.

10.50%

11.00%

CO Max.

100 ppm

100 ppm

e) Press the LEFT and RIGHT buttons to adjust the firing rate from 1% to 100%.Hold down

the LEFT or RIGHT but-ton to rapidly increase or decrease the firing rate.

f) Press the OK button while the FAN icon is highlighted to shut-down the burner.
g) Cycle power to the boiler once combustion testing is complete to return to normal

operation.

WARNING!

The combustion levels should be measured at high firing rate. If

the combustion levels are outside the range given in Table 12-1 for

the firing rate, shut the boiler down and contact AERCO Technical

Support. Failure to comply with this requirement could result in

severe personal injury, death, or substantial property damage.

3. If the combustion levels during high fire (100%) are outside the recommended combustion

settings in Table 12-1, adjust the Throttle Screw (see Figure 12-2) as follows:

Counter-clockwise rotation: O

2

decreases and CO

2

increases

Clock-wise rotation: O

2

increases and CO

2

decreases.

4. Once the combustion level is set at high fire (100%), manually place the boiler into low fire

(1%) mode by pressing the LEFT button to adjust firing rate downward.

5. If the CO2 combustion level during low fire (1%) is not within +/- 0.2 of the combustion level

measured at high fire, adjust the plastic Offset Pressure Screw under the cover screw on

the top of the gas valve (see Figure 12-2).

6. Counter-clockwise adjustment of the Offset Pressure Screw at Low Fire:

Counter-clockwise rotation: O

2

decreases and CO

2

increases

Clock-wise rotation: O

2

increases and CO

2

decreases.