3 boiler air vent, 4 low water cutoff device – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 32

Advertising
background image

GF-135

Esteem 399 Low NOx Boiler

Chapter 5

OMM-0089_0A

Installation, Operation & Maintenance Manual

Boiler Piping

Figure 5-1: Pressure Relief valve and Boiler Drain Valve Installation

5.3 BOILER AIR VENT

This boiler is supplied with a special automatic air vent that will provide reliable operation in

purging air from the boiler. The hygroscopic cap supplied with the automatic air vent MUST

remain tight at all times on the air vent body. The hygroscopic cap has a membrane which

expands upon contact with water and seals the air vent until the membrane dries up due to new

air forming in the air vent.

Make sure to fully tighten the cap on the air vent on initial installation.

Never loosen the hygroscopic cap to allow air to escape the air vent. Air will exit with the

cap fully tightened in place.

If the hygroscopic cap is not fully tightened, water may leak from the cap. Simply tighten

the cap securely.

5.4 LOW WATER CUTOFF DEVICE

The Esteem boiler is equipped with a factory installed pressure switch type Low Water Cut Off

device.

The minimum operating system pressure allowable with this device is 10 psig.

Check local codes if a Low Water Cutoff Device is required. If so, determine if this device

meets the requirements of the local codes.

WARNING!

The Esteem boiler control system senses the system water

temperatures entering and exiting the heat exchanger to provide

protection against low water conditions where local codes and

jurisdiction do not accept a pressure device for low water

protection, they may accept these integral control functions as a

means of providing low water protection.

(Field Supplied)

Page 32 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14