2 option 2: two permanent openings to outside – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 24

Advertising
background image

GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Combustion Air/Venting

3.5.2.2 Option 2: Two Permanent Openings to Outside

Two permanent openings, one commencing within 12 inches of the top and one commencing

within 12 inches of the bottom of the enclosure, shall be provided. The openings shall

communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the

outdoors, as follows:

Where directly communicating with the outdoors or where communication to the outdoors

is through vertical ducts, each opening shall have a minimum free area of 1 sq. in./4000

Btu/hr. of total input rating for all equipment in the enclosure. See Figure 3-3.

Figure 3-3: All Combustion Air from Outdoors Through Ventilated Attic

Where communicating with the outdoors is through horizontal ducts, each opening shall

have a minimum free area of not less than 1 sq. in./2000 Btu/hr. of total input rating of all

equipment in the enclosure. See Figure 3-4.

Figure 3-4: All Combustion Air from Outdoors Through Horizontal Ducts

Page 24 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288