Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.4.8 DHW Priority Timeout (Default: OFF)

Figure 18-34: DHW PRIORITY TIMEOUT Menu

DHW Priority Timeout allows the installer to enter an optional time limit that a domestic hot water

call has priority over a central heating call when DHW Priority is set to Enabled. Press the LEFT

or RIGHT buttons to adjust the DHW Priority Timeout then press the OK button to store the

setting.
========================================================================

18.4.9 DHW Priority (Default: ENABLED)

Figure 18-35: DHW PRIORITY Menu

DHW Priority allows the domestic hot water priority function to be enabled or disabled. Press the

UP or down buttons to select Enabled or Disabled then press the OK button to store the setting.

Enabled: Domestic hot water calls will have priority over a central heating call. The boiler

setpoint will be set to the domestic hot water setpoint during a domestic hot water call. The

DHW circulator will be enabled and the heating circulators will be disabled during a

domestic hot water call.

Disabled: Domestic hot water calls will not have priority over a central heating call. The

boiler setpoint will be set to the domestic hot water setpoint when only a domestic hot water

call is present. The boiler setpoint will be set to the highest setpoint when simultaneous

domestic hot water and central heating calls are present. The DHW circulator will be

enabled during a domestic hot water call. The heating circulators will be enabled during a

central heating call.

WARNING!

Simultaneous domestic hot water and central heating calls will

result in the boiler operating at the highest target temperature when

DHW priority is set to disabled. The use of a mixing device on the

lower temperature zones may be required to protect the lower

temperature zones from damage.