15 modbus interface – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 169

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.9.15 Modbus Interface

The Modbus Interface allows a Building Management System (BMS) to directly connect to the

boiler. A BMS can read information from the boiler to determine its operating state, lockout

status, sensor readings, etc. A BMS can also operate the boiler by providing a setpoint.

Table 18-8: Modbus Configuration

Protocol

MODBUS RTU

Baud Rate

38400bps

Data Length

8

Parity

None

Stop Bit

1

Physical Layer

RS485 (2 wire)

Table 18-9: Supported Commands

DEC

HEX

Description

03

0x03

Read Holding Registers

04

0x04

Read Input Registers

06

0x06

Write Single Register

16

0x10

Write Multiple Registers

17

0x11

Report Slave ID

Table 18-10: Holding Registers (Read/Write)

Address

DEC (HEX)

Supported

Commands

Description

Byte:

Format

Notes

512

(0x00200)

0x03

0x06

0x10

CH Demand

MB:U8

LB:U8

Writing:

0= Modbus CH1 Demand has priority

over a DHW call.

255 = DHW call has priority over a

Modbus CH1 Demand.


Reading:

0 = No CH Calls Present.

255 = CH1 or CH2 Call Present.


Writing:

0 = End CH1 Demand.

255= Begin CH1 Demand.

A CH1 Demand lasts for 30 seconds

from the last successful write.

513 (0x201)

0x03

0x06

0x10

Maximum

Firing Rate

LB:U8

Value = Maximum Firing Rate %. This

register becomes active when 255is

written to register 512 (0x0200)

Page 169 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288