Initial start-up – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 25

Advertising
background image

INITIAL START-UP

20


3. Using the 16” manometer installed as per

Section 4.2.1, adjust the gas supply
regulator until a reading of 12” W.C. static
pressure is obtained.


4. Place the green ON/OFF switch in the OFF

position. Turn on AC power to the unit. The
temperature controller and annunciator
displays should light.


5. Put the temperature controller in manual

mode

NOTE:

For a review of control panel operating

procedures

,

see Section 3.


6. Change the firing rate (Pct) to 0.0%.

7. Place the green ON/OFF switch in the ON

position.


8. Change the firing rate (Pct) to 25%. This will

put the unit into the starting sequence.

NOTE:

On initial start-up or return to service from a

fault condition, a warm-up timer of 2

minutes is activated by the controller. This

prevents the BTU input from exceeding

400,000 BTUs/HR even though the control

signal may indicate a greater input.

9. Observing the 2 minute warm-up period

increase the firing rate in 10 % increments
while monitoring the gas pressure after
every increase. If gas pressure dips below
8.5” W.C. for FM gas trains and 8.9” for IRI
gas trains at any input percentage, stop and
raise the pressure. Once 100% is reached,
adjust the gas pressure for 8.5” W.C. or 8.9”
W.C.

NOTE:

If 8.5” W.C. for FM gas trains or 8.9” W.C.

for IRI gas trains cannot be obtained at the

100% firing rate, it will be necessary to stop

calibration and contact the local AERCO
representative in your area. Running the

unit on insufficient gas pressure will void the

warranty

10. Once 8.5” W.C. or 8.9” W.C. is set at the

100% level change the firing rate (Pct) to

30%. Insert the combustion analyzer probe
into the stack.

NOTE:

Always go to a percentage of firing rate

from the same direction, (i.e., 100% to 30%
or 30% to 20%). Whenever going to a firing

rate from below (i.e., 20% to 30%), first go
above then back down to the desired firing

rate. This is necessary due to hysteresis in

the air/fuel stepper motor. Hysteresis

causes the air/fuel valve to stop in a slightly

different position if the firing rate

percentage is approached from below or

above. This results in a difference in oxygen
readings for the same firing rate percentage

causing unnecessary recalibration.


11. Allow enough time for the combustion

analyzer to settle. Compare the measured
oxygen level to the oxygen range for intake
air temperature in Table 1.

Table 1

Inlet Air

Temp

Oxygen

Carbon

Monoxide

20

o

F

5.7 %

<50ppm

40

o

F

5.5 %

<50ppm

60

o

F

5.2 %

<50ppm

80

o

F

5.0 %

<50ppm

100

o

F

4.9 %

<50ppm

Combustion Oxygen Levels for a 30%

Firing Rate

12. If the measured oxygen level is within the

range in Table 1, no adjustment is
necessary. Proceed to step 17.


13. If the measured oxygen level is below the

range in Table 1, rotate the differential
regulator adjustment tool counter clockwise
1/4-1/2 revolution to decrease gas flow.


14. Wait for the combustion analyzer to settle,

then compare the new oxygen reading to
Table 1. Repeat adjustment until oxygen is
within the specified range.


15. If the measured oxygen level is above the

oxygen range in Table 1, rotate the
differential regulator adjustment tool
clockwise 1/4-1/2 revolution to increase gas
flow.

Advertising