MODE OF OPERATION

27

from an external source, the following functions
must be correctly set.

MENU FUNCTION

SETTING

Secondary Lore

re

Secondary FUNC

Cont

Primary

Auto

OFF

5.5.1 BOILER MANAGEMENT SYSTEM
EXTERNAL FIELD WIRING

Wiring for this system is from the BMS panel to
terminals 2 and 3 in the unit’s external field
wiring box. Wire the units using a twisted pair of
22 gauge minimum wire. No shield is necessary.
When wiring multiple units, each unit’s wiring
must conform to the above. For a complete BMS
wiring diagram, see wiring schematic #18973
located in Appendix H.

5.5.2 BOILER MANAGEMENT SYSTEM
SETUP AND STARTUP

This mode of operation is factory preset and the
firing rate is controlled by the AERCO BMS
Model 168. There are no setup instructions for
each individual unit. However the unit must be
taken out of remote mode, and set to local
mode, to manually run the unit. Once finished
with manual mode it is necessary to set the unit
back to remote mode for it to be controlled by
the BMS.

To set the unit in local mode do the following:
1. Access the temperature controller’s

secondary menu.


2. Scroll through the menu until "lore" is

displayed.


3. Use

the

⇑ ⇓ keys to set the temperature

controller to local. The yellow REM light, on
the temperature controller, should extinguish


4. Press ENTER to accept the change.

5. Follow the above directions to change back

to remote mode.

NOTE:

The unit automatically defaults to remote

mode upon AC power being applied. This is

due to the presence of the external

interface board.

5.6 COMBINATION CONTROL SYSTEM
(CCP)

A Combination Control System is when enough
units are installed to cover the space-heating
load on the design day. However one or more of
the units are used to heat domestic, water while
the remaining units take care of the heating load.
The units used for the domestic hot water are
designated as the combination units and are
referred to as the combo units. The combo units
heat water to a constant setpoint temperature
that is circulated through a heat exchanger in a
domestic hot water tank.

An AERCO BMS 168 panel, a Combination
Control Panel (CCP), and the units are
interfaced in this mode of operation. When the
space heating units are all at 100% firing rate,
the BMS asks the CCP to switch the Combo
boilers to space heating mode. If the domestic
load is satisfied, the aquastat on the domestic
tank is open, the combo units will switch over to
space heating. If the domestic load is not
satisfied, the combo units remain on the
domestic load. If the combo units switch over to
space heating but there is a call for domestic hot
water, the CCP switches the combo units back
to the domestic load.

When the combo units are satisfying the
domestic load, they are in constant setpoint
mode of operation. When the combo units switch
over to space heating, their mode of operation
becomes BMS mode. For more information
concerning the operation of the Combination
Control Panel, see the AERCO CCP-1 literature.

In CCP mode, the external interface board is
utilized. The interface board, located in the field
wiring box, is factory configured, and converts
the pulse width modulation signal, sent from the
BMS, to an RS-485 signal. The RS-485 signal is
then sent to the temperature controller. For the
temperature controller to recognize a signal,
from an external source, the following functions
must be correctly set.

MENU FUNCTION

SETTING

Secondary Lore

re

Secondary FUNC

Cont

Primary

Auto

ON