APPENDIX E

xiv

BOILER DEFAULT SETTINGS

CONSTANT SET POINT MODE

MENU LEVEL

& CODE

DESCRIPTION OF CODE

FACTORY

DEFAULT

PRIMARY MENU

tout

OUTLET TEMPERATURE

ACTUAL

pct

PERCENTAGE OF FIRING RATE

ACTUAL

setp

UNIT’S SETPOINT TEMPERATURE

120

airt

OUTSIDE AIR TEMPERATURE

ACTUAL

auto

AUTOMATIC\MANUAL MODE

AUTO ON

SECONDARY MENU

func

MODE OF OPERATION

CONT

OAST

OUTSIDE AIR SENSOR FEATURE

OFF

OAT

OUTSIDE AIR TEMP

0

LLT

LOW LIMIT TEMPERATURE

40

HLT

HIGH LIMIT TEMPERATURE

220

pb1

PROPORTIONAL GAIN

70

int

INTEGRAL

1

drt

DERIVATIVE

0 (off)

addr

ADDRESS

32

lore

LOCAL/REMOTE MODE

LOC

SECURE

secr

SECURITY LEVEL

3

func

MODE OF OPERATION

CONT

gain

GAIN

1

pb3

PROPORTIONAL BAND

5000

lofi

LOW FIRE

29

lfti

LOW FIRE TIMER

0

purg

PURGE

100

O2-O

STOP LEVEL

16%

O2-C

START LEVEL

20%

FLTI

FAULT TIMER

0 SEC.

DFIL

DISPLAY FILTER

5

ARUP

ANTI RESET WINDUP

ON

PEA

PEAK(Highest Temp. Unit Has Seen Since Reset)

ACTUAL

VAL

VALLEY(Lowest Temp. Has Seen Since Reset)

ACTUAL

INPC

INPUT CORRECTION

0

INPT

INPUT TIMER

0.2

FILT

SENSOR FILTER

2

UNIT

UNIT OF DISPLAY

F

ADDR

ADDRESS

32

BAUD

BAUD RATE

9600

INP

INPUT

CAL