Troubleshooting – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 52

Advertising
background image

TROUBLESHOOTING

47

8.6.5 SOLID STATE RELAY

1. Referring to Appendix I,Item #17, open the

control box and locate the solid state relay.

2. Locate wire 81 on terminal 3 of the relay.

Measure the AC voltage on terminal 3 when
the unit is attempting to start.

3. If 120VAC is measured on terminal 3 and

the blower still does not start, replace the
solid state relay.

4. If not 120VAC is not measured, replace the

combustion safeguard relay module.

8.7 SYSTEM FAULT

A system fault indicates when the unit faults
during the starting sequence, but prior to ignition.
An internal 30 second fault timer starts timing
when the unit start sequence is initiated. If
ignition is not reached within the specified time,
the Annunciator displays the message SYSTEM
FAULT LOW AIR PRESSURE or PURGE
INTERLOCKS depending on the cause. A
system fault usually occurs when the system
does not acknowledge either the safety shut-off
valve proof of closure switch, the blower proof
switch, or the air/fuel valve open switch.

8.7.1 Determining the

C

ause

8.7.2 Blower

8.7.3 Combustion Air Supply and Blower

Proof

Switch

8.7.4 Purge Interlocks

8.7.5 SSOV Proof of Closure Switch

8.7.6 Air/fuel Valve Open Proving Switch

8.7.7 Air/Fuel Valve not Rotating

8.7.8 Air/Fuel Valve Ignition Position Switch



Recommended Troubleshooting

Equipment

AC Voltmeter

Ohmmeter

8.7.1 DETERMINING THE

CAUSE

1. Clear the Annunciator and start the unit.

2. If the blower starts and the message

SYSTEM FAULT PURGE INTERLOCKS is
displayed proceed to section 8.7.4

3. If the blower does not start, and the

message SYSTEM FAULT LOW AIR
PRESSURE is displayed, proceed to section
8.7.2.

4. If the blower starts, and the message

SYSTEM FAULT LOW AIR PRESSURE is
displayed, proceed to section 8.7.3

5. If the unit does not fire, and the message

SYS FLT is displayed on the temperature
controller and the Annunciator, proceed to
section 8.7.8.

8.7.2. BLOWER

1. Disconnect power to the unit

2. Remove the cover plate from the AC wiring

box.

3. Locate wire #13 and the blower hot lead wire

inside the AC wiring box. These will be the
only two wires connected by a wire nut.

4. Remove the wire nut and separate wire #13

from the blower hot lead wire.

5. Connect an AC voltmeter between wire #18

and the unit frame.

6. Reconnect AC power to the unit.

7. Start the unit.

8. The AC voltmeter should display 120VAC.

9. If 120VAC is not displayed, replace the

control panel.


10. If 120VAC is displayed, check the capacitor

using an analog ohm meter or substitute the
capacitor.

11. If the capacitor checks okay or is substituted

and blower still does not start, replace the
blower.


8.7.3 COMBUSTION AIR SUPPLY AND
BLOWER PROOF SWITCH

1. If the unit has sealed combustion, check the

ducting for any signs of blockage

2. If combustion air is brought in through an

opening in a wall, be sure that the size of the
opening is adequate and that louvers are
open while the unit is firing.

3. If the combustion air supply is okay, remove

wires #17 and #24 from the blower proof
switch.

Advertising