Troubleshooting – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 49

Advertising
background image

TROUBLESHOOTING

44

8.5.5 FLAME DETECTOR

1. Disconnect AC power to the unit.

2. Remove the flame detector as per Section

7.3.


3. Check the detector for signs of erosion or

carbon build-up.


4. If the flame detector is eroded, replace it.

Otherwise, clean it using emery cloth.


5. Carbon build-up on the flame detector

indicates that unit may require combustion
calibration.


6. Check the combustion calibration settings as

per Sections 4.2 and 4.3.

8.5.6 IGNITION CIRCUIT

1. Disconnect AC power to the unit.

2. Close the manual leak detection valve,

located between the safety shut-off valve
and the differential pressure regulator, on
the unit’s gas manifold.

3. Using a spare ignitor, connect the ignition

cable directly to the ignitor.

4. Ground the ignitor to the frame of the unit.

5. Reconnect AC power to the unit.

6. Start the unit.

WARNING !

ELECTRIC SHOCK HAZARD. THE

SECONDARY OF THE IGNITION

TRANSFORMER HAS A POTENTIAL OF

6000 VOLTS. DO NOT HOLD OR TOUCH

ANY IGNITION CIRCUIT COMPONENTS

WHILE TESTING.


7. At ignition an arc should be observed. It

should last for approximately 15 seconds.


8. If there is no arc, disconnect AC power to

the unit.


9. Remove the ignition cable and check it for

continuity or loose connections.


10. Replace the cable if there is no continuity or

if there is a loose connection.

11. If the ignition cable is okay, remove the

ignition transformer cover plate.


12. Referring to system schematic 161413 in

Appendix H, locate wires #12 and #29.


13. Connect an AC voltmeter across wires #12

and #29.


14. Reconnect AC power to the unit and start

the unit.

15. At the ignition cycle check for 120VAC

across wires #12 and #29.


16. If 120VAC is observed across wires #12 and

#29, replace the ignition transformer.


17. If 120VAC is not observed on the AC

voltmeter during the Ignition cycle,
disconnect AC power to the unit.


18. Disconnect the 9 pin connector from the

control panel, and wires #12 and #29 from
the ignition transformer.


19. Remove the cover plate from the AC wiring

box.

20. Referring to system schematic 161413 in

Appendix H, check wires #12 and #29 for
continuity.


21. If wires #12 and #29 have continuity, inspect

the pin on wire #12 in the 9 pin connector for
proper insertion or signs of wear.


22. Inspect the connector on wire #29 at the AC

wiring box end for a loose connection.


23. Make any necessary repairs.

24. After all wiring and connections have been

inspected or repaired, reconnect wires #12
and #29 to the ignition transformer.
Reconnect wire #29 to its proper position in
the AC wiring box.


25. Reconnect the 9 pin connector to the control

panel ensuring it is locked into place.


26. Reinstall the cover plates on the ignition

transformer and the AC wiring box.


27. Be sure to reinstall the spark ignitor and

ignitor contactor if necessary and reconnect
the ignition cable to the ignition transformer
and the ignition contactor.


28. Reopen the leak detection valve.

Advertising