Boiler default settings, Appendix e, Indoor /outdoor reset mode – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 71

Advertising
background image

APPENDIX E

xv

BOILER DEFAULT SETTINGS

INDOOR /OUTDOOR RESET MODE

MENU LEVEL

& CODE

DESCRIPTION OF CODE

DEFAULT

VALUE

PRIMARY MENU

tout

OUTLET TEMPERATURE

ACTUAL

Pct

PERCENTAGE OF FIRE RATE

ACTUAL

SEtP

UNIT’S SETPOINT TEMPERATURE

120

Airt

OUTSIDE AIR TEMPERATURE

ACTUAL

Auto

AUTO\MANUAL MODE

AUTO ON

SECONDARY MENU

Func

MODE OF OPERATION

OART

rEFt

BUILDING REFERENCE TEMPERATURE

70

rr

RESET RATIO

1.5

OASt

OUTSIDE AIR SENSOR FEATURE

OFF

OAt

OUTSIDE AIR TEMP

0

LLt

LOW LIMIT TEMPERATURE

40

HLt

HIGH LIMIT TEMPERATURE

220

Pb1

PROPORTIONAL GAIN

70

Int

INTEGRAL

1

drt

DERIVATIVE

0 (off)

Addr

ADDRESS

32

LOrE

LOCAL/REMOTE

LOC

SECURE MENU

SECr

SECURITY LEVEL

3

Func

MODE OF OPERATION

OART

gAin

GAIN

1

Pb3

PROPORTIONAL BAND

5000

LoFi

LOW FIRE

29

LFti

LOW FIRE TIMER

0

Purg

PURGE

100

O2-O

STOP LEVEL

16%

O2-C

START LEVEL

20%

FLti

FAULT TIMER

0 SEC.

dFiL

DISPLAY FILTER

5

ArUP

ANTI RESET WINDUP

ON

PEA

PEAK

ACTUAL

VAL

VALLEY

ACTUAL

InPC

INPUT CORRECTION

0

InPt

INPUT TIMER

0.2

FiLt

SENSOR FILTER

2

Unit

UNIT OF DISPLAY

F

Addr

ADDRESS

32

bAUd

BAUD RATE

9600

InP

INPUT

CAL