Installation Instructions (cont’d)

Wiring

A CAUTION

Never use this viater heater unless it is completely full of

water. To prevent damage to the tank and heating ele­

ment, the tank must be filled with water. Water must

flow from the hot water faucet before turning on power.

You must provide all wiring of the proper sixe outside of the
water heater. You must obey local codes and. electric company

requirements when you install this wiring.

If you arc not familiar with electric codes and practices, or if you
have any doubt, even the slightest doubt, in your ability to con­
nect the wiring to this water heater, obtain the service of a com­
petent electrician. Contact your Scars salesperson to arrange for
a professional electrician.

AWARNING

WATER HEATERS EQUIPPED FOR ONE VOLTAGE
ONLY: This water heater Is equipped for one type voltage
only. Check the rating plate near the bottom access panel
for the correct voltage. DO NOT use this water heater
with any voltage other than the one shown on the model

rating plate. Failure to use the correct voltage can cause
problems which can result In DEATH, SERIOUS BODILY
INJURf, OR PROPERTY DAMAGE. If you have any ques­

tions or doubts consult your electric company.

A CAUTION

If wiring from your fuse box or circuit brealrer box was

aluminum for your old water heater, replace It with cop­

per wire. If you wish to reuse the existing aluminum wire,
have the connection at the water heater made by a com­
petent electrician. Contact your Sears salesperson to

arrange for a professional electrician.

1. Piovid.c a way to easily shut off the electric power when

working on the water heater. This could, be with a circuit
breaker or fuse block in the entrance box or a separate dis­

connect switch,

2. Install and. connect a circuit directly from the main fuse or

circuit breaker box. This circuit must be the right she and
have its own fuse or circuit breaker. Refer to the chart in the
“Product Specifications” section for the correct sixe wire and
fuse or circuit breaker,

3. If metal conduit is used for the grounding conductor:

A, The grounding electrode conductor shall be of copper,

aluminum, or coppcrclad aluminum. The material shall

be of one continuous length without a splice or joint.

B. Rigid metal conduit, intermediate metal conduit, or elec­

trical metallic tubing may be used for the grounding
means if conduit or tubing is terminated in fittings
approved, for grounding.

C, Flexible metal conduit or flexible metallic tubing shall be

permitted for grounding if all the following conditions arc
met:

1, The length in any ground, return path docs not exceed

6 feet,

2, The circuit conductors contained, therein arc protected

by overcurrent devices rated at 20 amperes or less,

3, The conduit or tubing is terminated in Fittings

approved for grounding.

For complete grounding details and all allowable exceptions,
refer to the current edition of the National FJectrical Code,
NFPA70.

4, A standard.

V”

cond.uit opening has been made in the water

heater junction box for the conduit connection.

3, Wiring Diagrams (See Wiring Diagrams Section) have been

supplied, showing the two most common types of connec­
tions between the water heater and. the power supply. You can
easily sec which type connection you have by removing the

junction box cover on top of the water heater,

A, Two WTre Counecticui Diagrams! is the most common

requiring you to simply connect red to red., black to black,
and the ground wire to the green ground screw in the junc­
tion box of the water heater,

B. Three Wire Counection Diagmau is used when you arc
connecting the water heater to power a supply that has a
“Time Clock” or “Off Peak” Meter, To make these connec­
tions refer to block i or 2 in this wiring diagram for the type
of system you h ave,

NOTE: If

you have purchased, a three wire comiectiou

water heater but yow are not on a “Time Clock” or “OIF
Peak” meter and have a standard two wire connection
power supply, simply follow the connection diagram in
block

3.

of the Three

W

j

«

Connection Diagram.

6. Use wire nuts and. connect the power supply wiring to the

wires inside the water heater’s junction,

7. The water heater must be electrically “grounded” by the

installer. A green ground screw has been provided, on the

water heater's junction box. Connect ground wire to this

location.

8. Replace the wiring junction cover using the screw provided.

14