Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF infiNET™

Switches

SET

When the mode selection switch is in the “SET” position, it is operating in
the SET mode. The LED will blink to indicate that the switch is in the SET
mode. Refer to the following table for a list of available functions when the
switch is operating in this mode.

NOTE: The SET mode is only intended for adjusting the delay time. Under
normal operation, the mode selection switch should be in the “RUN”
position.

SET Mode Button Functions

FUNCTION

-SW1RF/-SWS1RF

BUTTON PRESS

-SW4RF/-SWS4RF

BUTTON PRESS

Set the delay
time to zero
seconds.

Double-tap the Bottom
button.

Double-tap the Button 1.

Set the delay
time.*

Press and hold the
Bottom button for the
desired amount of delay.
Upon release, the LED
will flash to confirm.

Press and hold Button 1
for the desired amount of
delay. Upon release, the
LED will flash to confirm.

* The button must be held for longer than three seconds in order to set the time. Any shorter

time will be ignored, and the time that was previously set will remain.

After setting the preset value(s), return the mode selection switch to the “RUN”
position.

-SLVS1RF

The -SLVS1RF has one rocker button. The -SLVS1RF does not have a mode
selection switch. It will emulate the RUN mode of the -SWS1RF (even if connected
to a -SWS4RF) unless the mode selection switch of the master is set to “OFF”.

Restore Default
Settings

To restore the switch’s default settings (delay time equal to zero seconds), move the
mode selection switch to the “RUN” position. While holding the pushbutton (hold
“UP” on the -SW1RF and -SWS1RF, or hold Button 1 on the -SW4RF or
-SWS4RF), move the mode selection switch to the “SET” position and back to the
“RUN” position. Release the pushbutton. The LED will flash once to confirm that
the default values have been restored.

LED Behavior

The -SW1RF, -SWS1RF, -SW4RF, and the -SWS4RF have a single amber LED. Its
behavior is determined by the current state of the switch or the control system
program.

For reference, the LED can be in one of three intensity levels: OFF, LOW, and
HIGH.

The following table describes the LED pattern in all modes of operation.

Operations Guide - DOC. 6397A

infiNET Switches: Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF