Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance

I n s t a l l a t i o n & S e r v i c e M a n u a l

RSR/E Filter Change

RSR/E Sheet Metal Filter Replacement

WARNING

DISCONNECT THE UNIT FROM THE ELECTRICAL

POWER SOURCE BEFORE ATTEMPTING

ANY SERVICE

WARNING

THE STANDARD FILTER IS PROTECTED WITH AN

EXPANDED METAL FACE SCREEN. THIS IS

NEVER TO BE USED TO HANDLE THE FILTER.

IT IS ONLY FOR PROTECTION AGAINST AN

ACCIDENTAL TOUCH OF THE FILTER.

ONLY HANDLE THE FILTER BY THE FRAME.

Service: Removal and Replacement of RSR/E Filters

Note: All filters should be visually inspected for freight damage before installation. It is necessary to use two workers when

removing the filter and for installation to avoid twisting or separation of the media seals. Handle the filter only by the frame

and never place anything on the upstream filter side of the filter. Additionally, it is important to keep the filter level to prevent

any shearing force on the media itself.

For RSR/E Filters:

Tools Required: Phillips Head Driver, Battery Operated Drill, 3/16” hex head ball driver (2ea)

Step 1. With the power off, remove the diffuser screen by removing the 6 each 10-32x1/2 screws, then carefully place in a

safe location.

Step 2. Loosen the six 1/4x12 socket head screws far enough to rotate the eight filter clips 90°. The filter may be loose

enough to drop during this operation. If not, slowly pull the filter away from the knife-edge seal, taking care not to touch the

filter face during this operation. It is important to pull the filter slowly away from the seal, so that the gel remains in the filter

gel track.

Step 3. Carefully clean plenum assembly knife edge surface of residual gel material.

Step 4. Inspect filter for visible damage, if damaged set aside for replacement or repair.

Step 5. Inspect the gel seal, if reinstalling the removed filter. Determine if the gel has lost its ability to seal (i.e. the gel should

reform to cover the track without voids or openings), if so repair the gel material or consider replacement of filter.

Step 6. Place the filter evenly against the filter-sealing surface of the RSR unit. Reposition filter clips and screws. The

clips should be rotated and angled into place. It is recommended that four workers work on each corner of the filter

simultaneously, holding the filter seated into the track. Hand tighten clips from opposite corners evenly until all clamps are

tightened.

Step 7. Reinstall diffuser screen by hand-tightening the screws.

Step 8. Determine if recertification or testing of replacement is required.

Step 9: Restore power to FFU and verify proper operation of FFU.

Filter

Filter Clip

¼ -20

Cap

Screw

10-32

PHP

Screws

Knife- Edge

Seal

Gel Track

Diffuser

Screen

Fan Filter Unit

Filter Clip and

Screw (typ 6)

2-Piece Welded

Plenum Housing

Diffuser Screen

Screws (typ 6)