Mac 10, Fan filter unit, Critical operation conditions of the mac 10 iq – Envirco MAC 10 IQ User Manual

Page 3: Part numbers covered by this manual

Advertising
background image

MAC 10

®

IQ

Fan Filter Unit

3

Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance

I n s t a l l a t i o n & S e r v i c e M a n u a l

Critical Operation Conditions of the MAC 10 IQ

1. Touching of the HEPA filter will damage it, voiding the warranty on the filter. The screen is only to protect against an

accidental ‘touch’ of the filter. Never place a hand or tool on the filter. Never lie filter face flat down on a surface always

have filter on its side to protect from damage.

2. Prior to powering the unit, verify voltage on label and that the unit has been wired into the correct voltage. The serial

number label on the top of the Mac 10 IQ unit has the required voltage.

3. To insure you order the proper replacement parts or complete MAC 10 IQ unit, record the part number and serial number.

This information is located on the serial number label, located adjacent to the electrical box. If you can’t locate the Sales

Order Number, please contact Envirco for this information. Once obtained, record the information for reference.

Part Numbers Covered by this Manual

MAC 10 IQ Standard

P/N

2x4

11074-XXX

2x3

11084-XXX

2x2

11083-XXX

MAC 10 IQ RSR

P/N

2x4

11089-XXX

2x3

11087-XXX

2x2

11086-XXX

MAC 10 IQ RSRE

P/N

2x4

11089-ZXXX

2x3

11087-XXX

2x2

11083-ZXXX

MAC 10 IQ RX RSR

P/N

2x4

11124-XXX

2x3

TBA

2x2

11127-XXX

MAC 10 IQ RX RSRE

P/N

2x4

11124-ZXXX

2x3

TBA

2x2

11127-ZXXX

Units come set in manual mode from

the factory. Please review installation

requirements and set up with your end user

(See page 8 for complete set up instructions).