TN1002

MAC10

®

Design with VAV Boxes

MAC 10 designs with Duct Collar, VAV or constant air box and fan coils

For applications requiring powered fan filter units and a ducted connection our recommendations

would be to use the MAC10 LEDC (ECM motor) or Mac10 Original ( PSC motor)

Feature

»

MAC10 LEDC

- Power conservation and high airflow

»

MAC10 Original

- Lower unit cost

Caution

»

MAC10 IQ is not recommend for the above design

For applications when you use a VAV box or Constant Airflow Terminal, Duct Collars or Fan

coils. The design engineer must advise the contractor or air balancer that the air supply

needs to be balanced. If you do not balance the air supply properly you have the potential

to starve or over feed the fan with air causing the motor to stall which can damage the fan

motor. This also can be minimized by notifying Envirco beforehand for assistance. The ECM

motors used in the IQ design are a Microprocessor controlled motor and are designed to

maintain a constant air volume. When two controllers are compensating the air volume at

the same time, the motor microprocessor is unable to stabilize the airflow and will shut itself

down if it cannot find a stable operating point.

In addition to properly balancing the airflow to the Fan: you should prepare a sequence of

operations turning on FFU’s prior to energizing the Air Handler to prevent potential backward

rotation of the blower wheel which can prevent motor rotating in the proper direction and will

reduce airflow and cause eventual shutdown. The drive components inside the ECM motors

are self-testing and sized for the motor being used inside the unit they can’t compete with the

airflows from a duct blower motor.

©2013 Envirco

®

. Envirco

®

is a registered trademark of Air System Components, Inc. All product specifications reflect available information at the printing of this brochure.

Envirco

®

reserves the right to revise or modify products and/or specifications without notice.

Envirco USA

101 McNeill Road

Sanford, NC 27330, USA

Tel: 919.775.2201

Toll Free: 800.884.0002

Fax:800.458.2379

www.envirco.com

email: [email protected]

European Sales

The Cavendish Centre

Winnall Close

Winchester, Hampshire,

S023 OLB, UK

Tel:+44(0)1962.840465

Fax:+44(0)1962.828619

www.envirco.com

email: [email protected]

Asian Sales and Manufacturing

Building #1

No.19 Xiangpu Road, Shenpu, SIP

Jiangsu Province, PRC 215021

Tel: +86.512.62967272

Fax: +86.512.62967221

email: [email protected]

Advertising