Mac 10, Fan filter unit, Limted warranty – Envirco MAC 10 IQ User Manual

Page 27: Testing

Advertising
background image

MAC 10

®

IQ

Fan Filter Unit

27

Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance

I n s t a l l a t i o n & S e r v i c e M a n u a l

Limted Warranty

LIMITED WARRANTY: Unless otherwise expressly stated

in Envirco’s published specifications for the Goods, Envirco

warrants that Goods are free from defects in material and

workmanship, except for services which are warranted to be

performed in a competent and diligent manner in accordance

with any mutually agreed specifications. The foregoing

warranty shall apply for eighteen (18) months from the date

of shipment from Envirco’s facility, except for services for

which the warranty shall apply for ninety (90) days from

the date of performance (the “Warranty Period”). Provided

Buyer informs Envirco in writing of any breach of warranty

prior to the expiration of the applicable Warranty Period,

Envirco shall, as its sole obligation and Buyer’s sole and

exclusive remedy for any breach of this warranty, repair or

replace/re-perform the Goods which gave rise to the breach

or, at Envirco’ option, refund the amounts paid by Buyer

for the Goods which gave rise to the breach. Any repair,

replacement or re-performance by Envirco hereunder shall

not extend the applicable Warranty Period. The parties shall

mutually agree on the specifications of any test to determine

the presence of a defect. Unless otherwise agreed upon by

Envirco in writing, Buyer shall bear the costs of access, de-

installation, re-installation and transportation of Goods to

Envirco and back to Buyer. These warranties and remedies

are conditioned upon (a) the proper storage, installation,

operation, and maintenance of the Goods and conformance

with the proper operation instruction manuals provided by

Envirco or its suppliers or subcontractors, (b) Buyer keeping

proper records of operation and maintenance during the

applicable Warranty Period and providing Envirco access to

those records, and (c) modification or repair of the Goods

only as authorized by Envirco. Envirco does not warrant the

Goods or any repaired or replacement parts against normal

wear and tear or damage caused by misuse, accident, or

use against the instructions of Envirco. Any modification or

repair of any of the Goods not authorized by Envirco shall

render the warranty null and void. EXCEPT AS EXPRESSLY

SET FORTH HEREIN, ENVIRCO MAKES NO OTHER

WARRANTIES, EXPRESS OR IMPLIED, INCLUDING,

BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES

OF MERCHANTABILITY, NON-INFRINGEMENT OR

FITNESS FOR A PARTICULAR PURPOSE WHICH ARE

HEREBY DISCLAIMED TO THE EXTENT PERMITTED BY

APPLICABLE LAW.

Testing

Each MAC 10 IQ filter unit is thoroughly tested at the factory

before shipment. However, because of the “rigors” of

shipping, ENVIRCO encourages its re-test after installation.

ENVIRCO recommends that the customer contact an

independent organization, with technicians trained and

experienced in performance evaluation and maintenance of

clean air equipment.

HEPA filters (Type J) are tested to IEST-RP-00034. ULPA

filters are tested to (Type F) IEST-RP-00034. All filters are UL

900 recognized. Your filters may have special requirements,

please see original engineering specifications for you specific

project.

All units that are airflow tested at Envirco are tested using a

Shortridge Airdata Multimeter 870 with a Velgrid head. The

recommended method of reading is to place one corner of

the Velgrid head 1-1/4” from the corner of the filter face and

then take four reading evenly spaced along the four foot side,

then repeat these reads three additional times. This gives a

total of 8 reading to test the unit. All advertised data is based

on using the Velgrid with 8 readings (128 velocity points).

Envirco recognized the using 8 reading during a cleanroom

start-up may be time consuming and recommends using

4 Velgrid readings taken on each 2x2 filter section will

approximate the same as 8 readings.

Additional independent testing on the Envirco Mac 10 IQ 2x4,

2x2, and 2x3, shows that using one-2x4 or two-2x2 hoods

simultaneously give airflow data (cfm) with 5 percent of a

duct traverse using 10 diameters of straight duct upstream

of the fan intake.

Advertising