Important – Chamberlain EL25 User Manual

Page 4

Advertising
background image

Page 3

Factory

Setting

Description of Task

Programming Procedure

Programming

Number

61 # (door 1-4) # (relays to activate 0000-1111) #

Order of relay is: relay 4 – relay 3 – relay 2 – relay 1 for an
example if you want relay 4 active you would enter 1000, if
you want relay 1 active you would enter 0001

60 # (device 1-4) # (device type 0-2; 0 = no device,
1 = wiegand card reader or keypad, 2 = RF receiver) #
(door 1-4) #

Delete an Entry Code

57

Assign Each External Access Control
Device a “Door Number”

(Step 1 of 4)

60

Assign “Each” Door Number to One or
More Relays

(Step 4 of 4)

61

Assign Door Use Time Zone

63

57 # (entry code) #

Set the Default Facility Code

73

73 # (0-255) #

Set the Default Card Type

71

71 # (26 or 30) #

Set Relay(s) for AutoCall

70

Assign a Postal Lock Switch to Door No.

69

69 # (door 0-4; 0 = no postal lock) #

70 # (relays to activate 0000-1111) #
Order of relays are 4321

63 # (door 1-4) # (time zone, 0-63) #

D1,D2,D3,D4=Enabled

No Device

Assigned

No Relays

Assigned

D1=Relay 1
D2=Relay 2
D3=Relay 3
D4=Relay 4

64

64 # (device 0-4) # (0-3; 0 = disable,
1 = set device to timed anti-passback,
2 = set device to true anti-passback - entrance,
3 = set device for true anti-passback - exit) #

Set Anti-Passback Entry/Exit for
Specific Devices

74

74 # (0 = disable; 1 = ignore) #

66 # (relay number 1-4) # (activation time, 1-300
seconds) #

Enable/Ignore Facility Code when Card is Used

66

Set Each Relay's “Activation Time”

(Step 3 of 4)

80

Add a Basic Card

81

Add or Edit a Full Function Card

67

Configure an Exit Device (REX)

Disabled

All Relays =“Strike”

All Relays =

10 seconds

R1=Door 1
R2=Door 2
R3=Door 3
R4=Door 4

68

Configure a Door Sensing Device

82

Add a Card Group

DS1=Door 1
DS2=Door 2
DS3=Door 3
DS4=Door 4

Set Each “Relay Type” to get the
Appropriate Response

(Step 2 of 4)

65

65 # (relay 1-4) # (0-5; 0 = unknown, 1 = strike,
2 = shunt, 3 = CCTV, 4 = alarm, 5 = control) #

Door 1

30-bit Cards

0

Ignored

The Pound Key (#) must be used as Data Field Separator and to Save Data at the end of the sequence.
Time must be entered using a 24-hour format

(8AM=0800, 3PM=1500 etc.)

2 Short Beeps:

Programming input is valid.

1 Long Beep:

Input is not valid.

If you make an error during an entry, press the asterisk key (

*

) to begin again.

Important:

Optional Steps Indicated with a Background, all other steps are Required

67 # (REX number 1-4) # (select REX option: 0 =
disabled, 1 = use your door settings or 2 = use
specific relay(s) 0000-1111) #
Order of Relays are 4321

68 # (sensor number 1-4) # (select sensor option: 0 =
disabled, 1 = use your door settings or 2 = use
specific relay(s) 0000-1111) #
Order of Relays are 4321

80 # (card PIN code) # (facility code) # (card type, 26
or 30) #

81 # (card PIN code) # (facility code) # (card type, 26
or 30) # (schedule for door 1, 0-63) # (schedule for
door 2, 0-63) # (schedule for door 3, 0-63) #
(schedule for door 4, 0-63) #

82 # (card PIN code start range) # (card PIN code
end range) # (facility code) # (card type, 26 or 30) #
(0 = deactivate; 1 = activate) # (schedule for door 1,
0-63) # (schedule for door 2, 0-63) # (schedule for
door 3, 0-63) # (schedule for door 4, 0-63) #

Advertising