Chimney requirements - offset installations, Odshr outdoor woodburning fireplace, 30˚ elbow offsets – CFM Corporation ODSHR42 User Manual

Page 6: Illustration key

Advertising
background image

6

ODSHR Outdoor Woodburning Fireplace

20002264

Chimney Requirements - Offset Installations

0 0 0 0 0

3"

11"

1 0 0 0 0

8¹⁄₄"

20"

0 1 0 0 0 11¹⁄₄" 25¹⁄₄"
2 0 0 0 0 13¹⁄₂" 29¹⁄₄"
1 1 0 0 0 16¹⁄₂" 34¹⁄₄"
0 0 1 0 0 20¹⁄₄" 40³⁄₄"
2 1 0 0 0 21³⁄₄" 43¹⁄₂"
0 0 0 1 0 26¹⁄₄" 51¹⁄₄"
0 1 1 0 0 28¹⁄₂" 55¹⁄₄"
1 0 0 1 0 31¹⁄₂" 60¹⁄₄”
0 1 0 1 0 34¹⁄₂" 65¹⁄₂"
0 0 2 0 0 37¹⁄₂" 70³⁄₄"
1 1 0 1 1 41¹⁄₂" 77³⁄₄"
0 0 1 1 1

45" 83³⁄₄"

0 1 2 0 1 47¹⁄₄" 87¹⁄₂"
0 0 0 2 1

51"

94"

0 1 1 1 1 53¹⁄₄"

98"

0 0 3 0 1 56¹⁄₄" 103¹⁄₄"
0 1 0 2 1 59¹⁄₄" 108¹⁄₂"
0 0 2 1 1 62¹⁄₄" 113¹⁄₂"
0 1 3 0 1 64¹⁄₂" 117¹⁄₂"
0 0 1 2 1 68¹⁄₄" 124"
0 1 2 1 1 70¹⁄₂" 128"
0 0 0 3 1 74¹⁄₄" 134¹⁄₂"
0 1 1 2 2

78" 140³⁄₄"

0 0 3 1 2

81" 146"

0 1 0 3 2

84" 151¹⁄₄"

0 0 2 2 2

87" 156¹⁄₂"

0 1 3 1 2 89¹⁄₄" 160¹⁄₄"
0 0 1 3 2

93" 166³⁄₄"

0 1 2 2 2 95¹⁄₄" 170³⁄₄"
0 0 0 4 2 99¹⁄₄" 177³⁄₄"
0 1 1 3 2 101¹⁄₄" 181³⁄₄"
0 0 3 2 2 104¹⁄₄" 186¹⁄₄"
0 1 0 4 2 107¹⁄₄" 191¹⁄₂"
0 0 2 3 2 110¹⁄₄" 196³⁄₄"
0 1 3 2 3

114" 203¹⁄₄"

0 0 1 4 3 117³⁄₄" 209³⁄₄"
0 1 2 3 3

120" 213¹⁄₂"

0 0 0 5 3 123³⁄₄" 220"

30˚ Elbow Offsets

1' 1¹⁄₂' 3'

4'

Chimney

Support

Offset

Rise

Notes: G + H cannot exceed 20 feet (610cm).
*11CF Chimney airspace clearance = 2" (51mm) minimum.

Illustration Key

The following safety rules apply to offset
installations (letters correspond with illustra-
tion above):
A. Height of the chimney is measured from
the hearth to the chimney exit.

ODSHR42

Maximum:

90' (27.4 m)

Minimum:
Without Elbows

14'6" (4.4 m)

With 2 Elbows*

15'6" (4.7 m)

With 4 Elbows*

21'0" (6.4 m)

B. Do not use more than 4 elbows per
chimney.
Attach the straps of the return (top) elbow
to a structural framing member.
The offset (first) elbow of any pair does not
have straps.
C. The chimney cannot be more than 30˚

FP269

from the vertical plane in any installa-
tion.
D. The maximum length of the angled
run of the total chimney system is 20
feet. (G plus H cannot exceed 20 feet.)
E. A chimney support (Model 11CS)
is required every 6 feet of angled run
of chimney. Chimney supports are
required for every 30 feet and 60 feet
chimney height above the hearth.
Determine the offset distance of your
chimney arrangement from the center-
line of the fireplace to the centerline of
the chimney where it is to pass through
the first ceiling.

NOTE: This offset distance may not be
your full offset distance. See Examples
2 and 3.

IWF282

MBUF

5/26/96

OFFSET

RISE

IWF282

Fig. 6 Chimney system requirements.

D

RISE

B

G

H

B

OFFSET

C

E

6 FT.

G

H

A

HEARTH

FLOOR

CHIMNEY

SECTION

CHIMNEY FLUE EXIT

ELBOW

IWF269
MBUF

5/16/96

rev. 5/25

30˚

OFFSET

ELBOW

30˚

OFFSET

ELBOW

30˚

RETURN

ELBOW

30˚

RETURN

ELBOW

11CS

SUPPORT

Example 1

Example 2

Example 3