LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 24

Advertising
background image

Page 24

LAARS Heating Systems Company

6.4 Setpoint Menu

The setpoint menu is accessed by pressing the

enter button, and holding it for 3 seconds. Move

through the setpoint parameters by pressing the up

and down arrows. When the desired parameter is

displayed, press the enter button. Use the up and down

arrows to change the value of that parameter, and press

enter to save the change. Parameters that can be set on

the Endurance boilers are shown in the next sections.

The boiler control will automatically return to the

view mode if the control buttons are not pressed for 30

seconds.

6.4.1 “SP” Supply Temperature

Shown as “SP” in the control, the supply

temperature is the Burner Off Point. When the

temperature of the water that is leaving the boiler heat

exchanger reaches this setting, the Endurance shuts

off. If there is still a call for heat, it will energize again

when it reaches the Burner On Point. Default value is

190°F (88°C). It is adjustable from 170-220°F (77-

104°C) on EBP units, and from 155-220°F (68-104°C)

on the EDP/EDN units. SP has a fixed 10°F (6°C)

differential to the Burner Control Point. SP minus the

10°F (6°C) differential gives you the Burner Control

Point, which is the temperature the Endurance will

attempt to maintain, using its modulation features. The

differential between SP and the Burner On Point is

adjustable, using the Burner On Differential.

6.4.2 “PO” Pump Operation

This parameter, shown as “PO” in the selection

screen, allows the user to choose between the

Endurance pump running continuously (“Con”), or

running in the automatic mode (“Aut”) such that the

pump is energized only when there is a call for heat,

and has the option of a pump time delay when the call

for heat ends.

6.4.3 “Pd” Pump Delay

Pump delay is shows as “Pd” on the screen.

When pump operation “PO” parameter is set for

automatic (“Aut”), the user can choose the pump delay

time. This is the length of time that the Endurance

pump will run after the call for heat has ended. It can

be used to purge heat from the boiler, putting it into the

system or transfer tank. It is adjustable from 0 to 10

minutes, and the default value is 3 minutes.

NOTE: Some systems are designed such that the

Endurance pump will be left with only the internal

recirculation path when a call for heat has ended.

Make sure the system design is known before setting

a pump time delay, so that the water has a path

during the purge time.

6.4.4 “Oar” Outdoor Reset

Outdoor reset can be turned on and off using the

“Oar” parameter. You must have an outdoor sensor,

properly located, to use this function.

IMPORTANT NOTE: The Endurance outdoor reset

is limited, to ensure that internal water temperature

is high enough to prevent heat exchanger

condensation. EBP units are limited further, to keep

the temperature of the water in the 20 gallon transfer

tank high enough to serve the domestic water plate

heat exchanger at all times. This feature is not meant

to replace or mimic a system outdoor reset controller.

Figure 33. EBP Flow Schematic.

Advertising