LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 34

Advertising
background image

Page 34

LAARS Heating Systems Company

it is flashing three times, for ignition control lockout. If

it is, then that is a combustion lockout.
a. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from either an improper gas/

air ration (high or low CO

2

) or contamination

of the combustion air supply. If an improper

gas/air ratio is suspected refer to “gas valve

calibration (offset adjustment)” in Section 10.

If contamination of the air source is suspected,

check the vent system for leaks back into the

combustion air.

b. Poor flame sensor signal: The boiler control

board will lockout if the flame sensor is grounded

or if the flame signal it receives is less than 1 A

dc. To check for a grounded sensor, remove

the flame sensor wire (yellow) from the boiler

control board and check for continuity between

the yellow wire terminal and the combustion

chamber bottom pan. If there is continuity, the

flame sensor is grounded. An alternate way to

check for grounding of the flame sensor is to

check the ohms resistance between the yellow

wire terminal and the combustion chamber

bottom pan, using a meter set for at least 100,000

ohms. The resistance must be more than 250,000

ohms (some technicians have been confused

by meters which report infinite resistance with

what appears to them as double zeros; an infinite

resistance reading means there is no grounding

of the flame sensor.) If there is continuity, or

the ohms resistance is less than 250,000 ohms,

debris or moisture in the combustion chamber

may be the cause. To correct, carefully remove

the ignitor and flame sensor assembly. Look for

debris on the assembly where the flame rod exits

the ceramic tube. If debris exists, remove it. If

this area is clean, insert a pencil or other round

object into the flame sensor hole in the bottom

combustion chamber pan and roll it around

to clear any debris that may exist inside the

combustion chamber. Replace the ignitor/flame

sensor assembly, reconnect the yellow wire

and start the boiler. If lockout persists, check

the flame signal. The minimum flame current

necessary to keep the system from lockout is 1

microamp (A). There is no need to disconnect

anything to measure the flame current signal.

To measure the flame signal, connect an analog

DC microammeter to the FC terminals on the

ignition control, per Figure 37. The meter should

read 1A or higher. (If the meter reads below

“0” on the scale, the meter leads are reversed.

Disconnect and reconnect the meter for correct

polarity.) If the meter reading is less than 1A,

see the “poor combustion” section. (Check for air

leaks at inlet to blower.)

c. Inadequate gas supply: Before proceeding,

ensure that the gas supply has not been shutoff

or the LP tank (LP boilers) is not empty. Then,

reset the boiler and observe the operational cycle.

Approximately 20 seconds after the start of the

cycle, the GV LED on the boiler control should

light. If it does not, reset the boiler and check

for 24 VAC at the boiler control. If the voltage

is less than 20 VAC, and transformer voltage is

24 VAC replace the boiler control. If the voltage

is correct, connect a pressure gauge to the offset

pressure port on the gas valve. Reset the boiler

and observe the offset pressure at startup and

after 20 seconds. The pressure will be ~ -2 in.

w.c. at startup (during prepurge) and should

become less negative (-0.1 in. w.c.) when the gas

valve opens and gas flow starts. If the pressure

remains at ~ -2 in. w.c. throughout the cycle

replace the gas valve.

d. Ignitor failure: If the boiler goes through a

normal start cycle but combustion does not occur,

ignitor failure should be suspected.

Check the ignitor by unplugging the ignitor plug

and measuring the ignitor resistance. It should be

50-100 () ohms. If the resistance is not 50-100

ohms (), replace the ignitor. If the resistance is

correct, reset the boiler and check for 120 VAC

at the ignitor plug during the start cycle. If there

is no voltage, replace the boiler control or faulty

ignitor wires.

e. Blocked or contaminated air source: Before

proceeding, ensure that the vent terminal (Direct

Vent installations) or the air inlet (Category IV

installations) is not obstructed. In general, only

direct vent installations have the potential for

cross contamination (flue products entering the

combustion air stream) of the combustion air

source. This may be caused by leaky joints in the

3" flue pipe located inside the 5" combustion air

pipe. If this is suspected, remove the front panel

from the appliance, reset the boiler and allow it

Figure 37. Flame Sensor Current Check.

Advertising