LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 30

Advertising
background image

Page 30

LAARS Heating Systems Company

The control displays the supply temperature, by

default, and the user can access the heat exchanger

inlet temperature, tank temperature (EBP models), heat

exchanger delta T, outdoor air temperature (if reset is

used), and all of the setpoint and differentials that are

set on the boiler. 7 fault codes can also be displayed,

for diagnostic help.

To replace the boiler control, shut off 120V

power to the Endurance. Remove the two sheet metal

screws from the controller mounting bracket. Pull the

controller, attached to the mounting bracket out, to

access the electrical connectors.

Remove the electrical connectors from the

control. Pull out the tabs on the retaining clip, while

pulling the controller out through the front.

Replace in reverse order.

8.5 Ignition Control

The ignition control controls the hot surface

ignitor and proves that the flame signal is appropriate

for powering the gas valve. It also controls the

blower’s pre-purge and post-purge timing. It works

with the boiler control to ensure proper and safe

operation of the Endurance.

To replace the ignition control, shut off the

120-volt power to the appliance. Remove the cover

to the Endurance control panel. Remove the electrical

connectors from the ignition control. Take out the

controller’s mounting screws, and pull the controller

out. Replace in reverse order.

8.6 Ignitor / Flame Sensor Assembly

The ignitor is a hot surface ceramic composite

device. It is energized whenever there is a call for heat

and switched off when ignition is established.

The flame sensor is a remote sensing flame rod

which is connected directly to the ignition control. The

ignitor should read 50 to 100 ohms resistance when at

room temperature.

If the ignitor fails and the assembly must be

replaced, always install a new ignitor gasket with the

replacement assembly.

For sequence of operation, see Section 9.1,

Servicing.

Caution

Ignitor gets hot.

8.7 Transformer

The control transformer accepts 120 VAC line

voltage and provides 100 VA of 24 VAC control

voltage for the boiler control ONLY. It is NOT capable

of supplying control voltage for external devices such

as zone valves, which MUST have their own separate

power supply.

Should the transformer require replacing, shut off

the 120 volt power. Unplug the transformer wires from

the transformer, unscrew the two fixing screws and

remove the transformer.

Fit the replacement transformer in reverse order.

8.8 PWM Board

The PWM board converts the 0-10V modulating

signal that comes from the boiler control to the PWM

(pulse width modulating) signal that is sent to the

blower to control the blower speed, and hence, the

modulating point of the Endurance.

This board also converts 24V AC to 24V DC,

which is used to power the boiler.

To replace the PWM board, shut off the 120 volt

power. Unplug the two electrical connectors to the

PWM board. Depress the barbs on the four standoffs to

free the board, and pull it out. Replace in reverse order.

8.9 Blower

The combustion air blower is a high pressure

centrifugal blower. It is powered by a 24VDC motor

which is controlled by the boiler control with voltage

that has been converted by the PWM board. Its speed

will be varied according to the temperature of the

boiler flow.

If a blower change is required, turn off the 120

volt power and unplug the wires from the blower

motor. Remove the four nuts from the blower

discharge flange and the four screws that secure the

gas manifold to the gas valve. Remove the complete

assembly. Unscrew the combustion air inlet assembly

and register plate from the fan.

Fit the replacement fan in reverse order, ensuring

that all joints are made correctly and sealed.

After replacement the combustion should be

checked for correct air fuel ratio (see Section 10).

8.10 Transfer Tank (EBP)

The transfer tank contains approximately 20

gallons of boiler water. It functions as an energy

storage vessel to reduce boiler cycling on small output

heating zones and to provide additional heat for

domestic hot water through the domestic hot water

(DHW) plate heat exchanger.

If a tank change is necessary, access to the tank

is possible by removing the jacket’s front door. This

is done by removing the screws that hold the panel at

the top and lifting the panel away. Isolate the appliance

and drain down using the drain cock at the base of

the tank. Remove the tank sensor. Undo the union

and the pump flange bolts that connect the tank to the

boiler, unscrew the panel between the upper and lower

compartments, support the upper components and

remove the tank. Installation of the new tank is done in

the reverse order. After installation purge all air from

the boiler before restarting.

Advertising