LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 26

Advertising
background image

Page 26

LAARS Heating Systems Company

6.6.2 Alarm Acknowledge

When an alarm is activated (LO or one of the F

codes), the control will flash between the alarm display

and the supply temperature. Pressing the power button

(upper left button) for half a second will allow the user

to scroll through the menus for 30 seconds, before

reverting back to the alarm display.

6.6.3 Power On/Off

Pressing the power button on the control (upper

left button) for 3 seconds will turn the controller off.

This will not de-energize the boiler’s power, but will

de-energize the controller. The display will still work,

but the boiler will not acknowledge a call for heat, and

will not be able to fire. This allows the user to check

and set parameters when the boiler is unable to fire.

The display will show “OFF”. When the power button

is pressed again for 3 seconds, the display will show

“ON” briefly, and the boiler will then resume normal

operation.

6.6.4 Low Fire Hold

By pressing and holding the enter button and

the down arrow button for 2 seconds, the user will fix

the Endurance in low fire for 5 minutes. There is no

change in the boiler control display when the unit is in

this mode.

6.6.5 High Fire Hold

By pressing and holding the enter button and the

up arrow button for 2 seconds, the user will fix the

Endurance in high fire for 5 minutes. This can be used

to check and/or set combustion on the appliance. There

is no change in the boiler control display when the unit

is in this mode.

6.6.6 Pump Operation

The Endurance’s internal pump will operate

when any of the following conditions occur:

Low temperature mode.

Tank charge mode.

Heating system (T-T) call for heat.

Domestic hot water (DHW) call for heat.

Error condition detected.

Supply temperature detected as less than

“boiler on point”.

6.6.7 Anti-Condense Valve Operation

The control on the EBP unit opens and closes the

Anti-Condensing Valve (ACV) based on the following

boiler conditions:

ACV Open:

Heating system (T-T) call for heat, when

there is no tank charge or DHW call for

heat.

Cycles open and then closes every time the

EBP is powered up.

ACV Closed:

Domestic hot water (DHW) call for heat.

Tank charge mode.

No heating system (T-T) call for heat.

Button

Action

Result

Up Arrow

Press for 1/2 second

1. Scrolls up through view menu

(Upper Right Button)

2. In setup menu, scrolls up through setup menu

3. In setup menu, after parameter is chosen, increases

the value of that parameter

Down Arrow

Press for 1/2 second

1. Scrolls down through view menu

(Lower Right Button)

2. In setup menu, scrolls down through setup menu

3. In setup menu, after parameter is chosen, decreases

the value of that parameter

Enter

Press and hold for 3 seconds

Puts the control is setup mode

(Lower Left Button)
Enter

Press for 1/2 second

1. When in setup view, chooses the parameter that the

(Lower Left Button)

user wants to adjust

2. When in setup menu, saves an adjusted parameter

Enter & Up Arrow Together

Press both together for 2 seconds

High fire hold for 5 minutes

(Lower Left and Upper

Right Buttons Together)
Enter & Down Arrow Together Press both together for 2 seconds

Low fire hold for 5 minutes

(Lower Left and Lower Right

Buttons Together)
Power

Press for 1/2 second

When in alarm mode, allows the user to scroll through

(Upper Left Button)

menu for 30 seconds

Power

Press and hold for 3 seconds

Turns control off or on to allow programming without a

(Upper Left Button)

call for heat interruption.

Table 4. Boiler Control Button Functions.