LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 27

Advertising
background image

Endurance

Page 27

6.6.8 Field-Supplied Outdoor Reset

Controls

When a stand-alone outdoor reset control is used

with the Endurance, it will only have the ability to

reset the system water temperature, and start/stop a

call for heat. Although this will work, be aware that

this will likely cut into the modulation range that the

boiler control is calculating, because the boiler control

is not changing its temperature settings. This may

result in an Endurance that works like an on/off boiler,

rather than the modulating boiler, and may cycle on

and off more frequently than desired.

Endurance units have built-in outdoor reset

capability, with the addition of the outdoor reset

sensor. This will reset the boiler supply temperature,

while ensuring that the temperature is not dropped

enough to affect the EBP’s domestic water output, and

keeping the return temperature to the Endurance high

enough to prevent condensation on the heat exchanger.

IMPORTANT NOTE: The Endurance outdoor reset

is limited, to ensure that internal water temperature

is high enough to prevent heat exchanger

condensation. EBP units are limited further, to keep

the temperature of the water in the 20 gallon transfer

tank high enough to serve the domestic water plate

heat exchanger at all times.

SECTION 7.

Boiler Start Up

7.1 Removal of Boiler From

Common Vent

NOTE: This section does not describe a method for

common venting Endurance boilers. It describes

what must be done when a unit is removed from a

common vent system. Endurance boilers are

not

permitted to be common vented with any other

appliance(s), including other Endurance appliances.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances

remaining connected to the common venting system

are not in operation.

1. Seal any unused opening in the common venting

system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is

no blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe

condition.

3. Insofar as is practical, close all building doors

and windows and all doors between the space in

which the appliances remaining connected to the

common venting system are located and other

spaces of the building. Turn on clothes dryers

and any appliance not connected to the common

venting system. Turn on any exhaust fans, such

as range hoods and bathroom exhausts, so they

will operate at maximum speed. Do not operate a

summer exhaust fan. Close fireplace dampers.

4. Place in operation the appliance being

inspected. Follow the lighting instructions.

Adjust thermostat so appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening

after 5 minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting

system properly vents, when tested as outlined

above, return doors, windows, exhaust fans,

fireplace dampers and any other gas burning

appliance to their previous conditions of use.

7. Any improper operation of the common venting

system should be corrected so the installation

conforms with:

1. The applicable venting requirements of the

National Fuel Gas Code (ANSI Z223.1/

NFPA 54), latest edition; or

2. in Canada, The Natural Gas and Propane

Installation Code (CSA B149.1), latest

edition.

All applicable provisions of local building codes

should also be adhered to.

When re-sizing any portion of the common

venting system, the common venting system should be

re-sized to approach the minimum size as determined

using the applicable section of the latest editions of the

above-referenced installation codes.

7.1 Enlèvement de la chaudière du

système de ventilation commun

REMARQUE : Cette partie ne décrit pas une

méthode pour les chaudières Endurance à ventilation

commune. Elle décrit ce qui doit être fait lorsqu’une

unité est enlevée d’un système de ventilation

commun. Il n’est pas autorise aux chaudières

Endurance d’avoir un système de ventilation

commun avec tout autre appareils, y compris d’autres

appareils Endurance.

Au moment du retrait d’une chaudière existante,

les mesures suivantes doivent être prises pour chaque

appareil toujours raccordé au système d’evacuation

commun et qui fonctionne alors que d’autres appareils

toujours raccordés au système d’évacuation ne

fonctionnent pas:

1. Sceller toutes les ouvertures non utilisées du

système d’évacuation.

2. Inspecter de façon visuelle le système

d’évacuation pour déterminer la grosseur

Advertising