iNSTALL THE SENSORS

SYSTEM SENSOR (HSS) iNSTALLATiON

• Only use a Standard Brass Tube sensor (CA002400 or equivalent).

• The sensor wires can be extended up to 500' using a shielded 2-conductor cable

(Belden #8760 or equivalent). Do not ground the shield at the sensor but at the

panel using one of the terminals marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

• Install a 3/8"ID 1/2"NPT immersion well (CA002500 or equivalent).

• Insert the sensor in a well approximately 10' feet past the last boiler on the

common supply header but before any major takeoffs.

• The sensor must be located where it sees the output of all the boiler stages. If a

boiler is piped so that the sensor does not see its output, the M4-CNC will not

sequence the boilers correctly.

• The sensor can also be installed on the return to the boilers after all major returns

and before any boiler. However, when setting the reset ratio and the offset, the

user must consider the temperature drop across the building loop.

Immersion Well

3/8" ID 1/2" NPT

Heating System

Sensor

Common Supply Pipe

Sensor Probe

Immersion Heating System Sensor

Shield

Common Supply Pipe

Sensor Probe

Strap-On Heating System Sensor

Shield

Pipe Insulation

Connect

To control

ALERT

If the System Sensor can not sense the

correct water temperature, the

M4-CNC

will not provide comfortable heat levels.

OUTdOOR SENSOR iNSTALLATiON

• Only use the Laars sensor included with the unit (CA006500).

• Locate the sensor in the shade on the north side of the building. The sensor

should never be in direct sunlight.

• Be sure the location is away from doors, windows, exhaust fans, vents, or other

possible heat sources.

• The sensor should be mounted approximately 10' feet above ground level.

• Adhere the Outdoor Label provided to the back of the sensor base.

• Use the Enclosure Base bottom knockout for the conduit. Use the locknut to hold

the conduit and enclosure base together. Screw the cover to the base.

• If screws are used to affix the enclosure to the wall, make sure to seal around the

sensor and wall except from the bottom.

• The sensor wires can be extended up to 500' using shielded 2-conductor cable

(#18/2). Do not ground the shield at the sensor but at the control using the

terminal marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

ALERT

determining the proper location of the Outdoor Sensor is very important. The M4-CNC will base the

heat on the outdoor temperature information it receives from this location. if the sensor is in the sun, or

covered with ice, its reading will be different from the actual Outdoor temperature (Od).

System Sensor

In Well

Shield

Not connected

Well Locknut

Sensor

in Well

Well

Sensor 2-Conductor

Shielded Cable

System

Strap-On

Sensor

Shield

Not connected

Plastic

Tie-Wraps

Around Pipe

Outdoor

Sensor

snap-in

location

Shield

not connected

Conduit

Outdoor Label

on back of Sensor

Outdoor Sensor

Strap-On Sensor

Immersion Sensor

Mounting

screws

location

Seal around

sensor and wall

Outdoor

drip-hole

LAARS Heating Systems

HT# 059104-00 B