MOdULATiNg BOiLER SETTiNgS

MOdULATiNg OUTPUT TYPE

4-20mA, 0-5V, 0-10V, 1-5V, or 2-10V Outputs

Default: 4-20mA

• If either of the Condensing or Non-Condensing Boiler Groups was set to Modulating as the

Boiler Type, the M4-CNC will offer the capability of controlling a variety of modulating

signals. Each boiler can be configured to have a different modulating signal.

• The modulating output for each boiler can be configured to 4-20mA operation (Current)

or any of the voltage ranges (0-5V, 0-10V, 1-5V, 2-10V). Check the modulating boiler to

determine its control requirements.

• When using the M4-Extension, connect it to the M4-CNC prior to configuring the Output

Type. Otherwise, the M4-CNC might not recognize them properly.

MOdULATiNg MOdE

Normal, Parallel

Default: Normal

• Some modulating boilers perform better at higher modulation. For these units, it is

advantageous to run one unit at high modulation than several units at lower modulation. If

the units used are of this type, select Normal. This is the recommended setting for typical

steel and cast iron boilers or boilers with low turndown ratios.

CONDENSING

-- OUTPUT A TYPE --

4-20ma

0-10v

0-5v

2-10v

1-5v

Not Installed

BACK ▲ ▼ SAVE

WARNiNg

Make sure that boiler

modulation wiring matches the

signal selected. Warranty will

not cover failed components

caused by improper wiring.

See "Wiring to Modulating

Output" on page 13.

CONDENSING

- MODULATING MODE -

Normal

Parallel

BACK ▲ ▼ SAVE

• There are many condensing boilers that run more efficiently at lower modulation. If it

is more energy efficient to run several units at lower modulation than one at high, select

Parallel. This is typically used on water-tube boilers, low mass boilers, or boilers with high

turndown ratios.

• For best Parallel performance, set the Modulation Start % to be equivalent to the lowest

firing rate of the boiler multiplied by 2. That is, if the lowest firing of the boiler was 20%,

set your Modulation Start% to 40%. See "Modulation Start %" on page 32.

• If Parallel is selected, it is preferred to set the Lag Delay to 0. See "Lag Delay" on page 26.

LAARS Heating Systems

HT# 059104-00 B