System settings, Setback, Purge delay – LAARS M4-Ext - Installation Manual User Manual

Page 24: System run-on, Mini-mod, Alert, A b c d, 0 min, 5 min, Laars heating systems

Advertising
background image

24

SYSTEM SETTiNgS

Button: MENU/<System Settings>

Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for

enhanced comfort and better fuel savings. The M4-CNC behaves differently based on the

selected Control Modes. See "Startup Settings" on page 16.

----- SETTINGS 1 ----

Setback

0

o

F

Purge Delay 1.0min

System Run-On 0min

Lead Rotation Time

<More Settings>

BACK ▲ ▼ SELECT

----- SETTINGS 2 ----

Standby Time 10min

Last Stg Hold 0

o

F

<Lead Stages>

<Staging Settings>

<Mdlating Settings>

<Day/Night Schdule>

BACK ▲ ▼ SELECT

ALERT

To be able to change the

M4-CNC settings the Program/Run Switch must be set

to Program. The switch is located under the Enclosure Wiring Cover for security.

The Enclosure Wiring Cover can be securely closed using a lock.

SETBACk

Adjustable from 0F°/0C° to 75F°/42C°

Default: 0F°/0C°

Button: MENU/<System Settings>/Setback

• The Setback feature can be used to provide the M4-CNC with a lower temperature Set Point

when less load is required.

• The lower Set Point will appear on the main display indicating this condition.

• For example, if the calculated temperature is 180°F and the Setback is 20°F, then when in

Setback or Night Schedule, the M4-CNC will hold a Set Point of 160°F = 180°F- 20°F. See

"Day/Night Schedules" on page 28.

• A typical use for Setback is to provide less system temperature to a building during the

Night Schedule or on the weekends when the building is not occupied, but heat is still

required.

• The amount of Setback selected is subtracted from the Set Point when a Setback Input

Signal is received or the Night Time schedule setting started.

• If Setback is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/Setback

Mode" on page 19), the Setback will not be activated unless a Short dry-contact signal is

received on terminals (31 and 32).

• If Shutdown or Tstat is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/

Setback Mode" on page 19), the Setback will be activated only when the Night Schedule time

has started.

SYSTEM

A
B
C
D

Full Modulation Sequencing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

Mini-MOD

------- SETBACK -------

5

o

F

[

]

BACK ▲ ▼ SAVE

ALERT

When using Soft-Off and Last

Stage Hold, the last boiler

stage will not turn off until both

parameters have elapsed. In

this case, Soft-Off will start after

the Last Stage Hold.

PURgE dELAY

Adjustable from 0.0min to 10.0min

Default: 1.0min

Button: MENU/<System Settings>/Purge Delay

• Many boilers go through a purge cycle before they are brought on line. When the M4-CNC

activates a boiler, it does not start to calculate its output until the Purge Delay is over. This

allows the boiler to fully come online and begin producing output.

• The Purge Delay helps prevent short cycling of any newly activated burner. Once the

burner is activated, it MUST run through the entire Purge Delay period.

• The minimum Purge Delay setting MUST be set to the time required by the boiler

manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5min will equal 90 seconds.)

• The Message Display Line will display Purge Delay and the amount of Purge remaining.

--- PURGE DELAY ---

1.0 min

[

]

BACK ▲ ▼ SAVE

ALERT

Set Purge Delay as per boiler

manufacturer recommendation.

SYSTEM RUN-ON

Adjustable from 0min to 360min

Default: 0min

Button: MENU/<System Settings>/System run-On

• The SYS relay will energize whenever the outdoor temperature is below the Outdoor Cutoff

and the Shutdown is Open or the Tstat is closed. When the Outdoor temperature rises 2°F

above the Outdoor Cutoff or the control is switched to Summer and after the last burner

relay has de-energized, the SYS relay will remain energized for the System Run-On period.

-- SYSTEM RUN-ON --

5 min

[

]

BACK ▲ ▼ SAVE