WiRiNg THE BOiLERS

• When wiring condensing and non-condensing boilers make sure that condensing boilers utilize the first stages

and non-condensing boilers will utilize the following stages. That is, if the installation had two condensing

modulating boilers and two non-condensing staging On/Off boilers, Stage A and B will be used by the condensing

boilers while C and D will be used by the non-condensing boilers.

WiRiNg ON/OFF BOiLER OUTPUTS

(A TERMinALS 5, 6), (B TERMinALS 7, 8), ...

• Each boiler output (A through D) has one Normally Open (N.O.) relay contact.

• The N.O. contacts are dry contacts only. They do not source any voltage.

• Wire the N.O. relay contacts in series with the unit’s limit circuit.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

• Note that some modulating boilers may not require the use of these outputs.

SYSTEM

A
B
C
D

Condensing / Non-Condensing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

OD=

25

o

F

SYS=

145

o

F

<<A>>

B

100%

52%

Mini-MOD-CNC

Boiler Enable

Output

Boiler

WiRiNg MULTi-STAgE BOiLER OUTPUTS

(A TERMinALS 5, 6, 7, 8), ...

• Each stage output (A through D) has one Normally Open (N.O.) relay

contact that does not source any power.

• Wire each of the N.O. relay contacts to its respective boiler stage.

Note that on the display of the M4-CNC each staging boiler will

consist of multiple letters. The letters represent outputs that should

be wired to that boiler. The first letter should be wired to the lowest

firing stage and the next letter to the next stage and so on. See "Boiler

Status" on page 30.

• Class 1 voltages must enter the enclosure through a different opening

from any Class 2 voltage wiring.

OD=

55

o

F SYS=

142

o

F

<CD>

EF

LO

---

STAGE ◄ ► MENU

SYSTEM

A
B
C
D

Condensing / Non-Condensing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

OD=

25

o

F

SYS=

145

o

F

<<A>>

B

100%

52%

Mini-MOD-CNC

2-Stage Boiler

Stage1

Stage2

WiRiNg TO MOdULATiNg OUTPUT

The M4-CNC can modulate any combination of the following boiler signals. The Modulating Output Type must

be selected properly before connecting any output wires to avoid damaging components. See "Modulating Output

Type" on page 18. Some modulating boilers may require the use of the relay stage outputs. See "Wiring the Boilers"

WiRiNg THE 4-20MA MOdULATiNg MOTORS

(A TERMinALS 13, 14), (B TERMinALS 16, 17),...

• The M4-CNC can operate up to four 4-20 mA modulating motors.

• The M4-Extension can operate up to six 4-20 mA modulating motors.

• The M4-CNC and the M4-Extension sources 24VDC excitation voltage for the 4-20mA signal.

• Wire the (-) from the modulating motor to the boiler terminal on the M4-CNC marked (GND). That is for boiler

A, the modulating (-) terminal will be 13.

• Wire the (+) from the modulating motor to the boiler terminal on the M4-CNC marked (mA). That is for boiler A,

the modulating (-) terminal will be 14.

SYSTEM

A
B
C
D

Condensing / Non-Condensing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

OD=

25

o

F

SYS=

145

o

F

<<A>>

B

100%

52%

Mini-MOD-CNC

Boiler 4-20mA

Modulation Output

4-20mA

Burner

Motor

-

+

WiRiNg THE vOLTAgE MOdULATiNg MOTORS

(A TERMinALS 13, 15), (B TERMinALS 16, 18),...

• The M4-CNC can operate up to four 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.

• The M4-Extension can operate up to six 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.

• Wire the (GND) from the modulating motor to the boiler terminal on the M4-CNC marked (GND). That is for

boiler D, the modulating (GND) terminal will be 22.

• Wire the (V+) from the modulating motor to the boiler terminal on the M4-CNC marked (VLT+). That is for

boiler D, the modulating (V+) terminal will be 23.

SYSTEM

A
B
C
D

Condensing / Non-Condensing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

OD=

25

o

F

SYS=

145

o

F

<<A>>

B

100%

52%

Mini-MOD-CNC

Boiler Voltage

Modulation Output

Voltage

Burner

Motor

GND

V+

ALERT

To set the M4-Extension to a specific letter, remove the wiring cover and switch the Ext A/Ext B

to the desired letter. DO NOT set both extensions to the same letter to avoid errors.

LAARS Modulating Controls M4 & M4-EXT

HT# 059104-00 B